EDR-5000
IM02602007E
Parameter
Description
Setting range
Default
Menu path
ExBlo TripCmd Fc
Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo TripCmd Fc=active".
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/I-Prot
/50R[1]]
Criterion
Measuring method: fundamental or rms or 3rd harmonic
(only generator protection relays)
Fundamental,
True RMS
True RMS
[Protection Para
/<1..4>
/I-Prot
/50R[1]]
Pickup
If the pickup value is exceeded, the module/element will
be started.
0.02 - 20.00In
50R[1]: 1In
50R[2]: 2In
[Protection Para
/<1..4>
/I-Prot
/50R[1]]
t
Tripping delay
Only available if: Characteristic = DEFT
0.00 - 300.00s
0.5s
[Protection Para
/<1..4>
/I-Prot
/50R[1]]
www.eaton.com
517