EDR-5000
IM02602007E
Name
Description
AR.Service Alarm 2
Signal: AR - Service Alarm 2, too many switching operations
AR.Max Shots / h exceeded
Signal: The maximum allowed number of shots per hour has been exceeded.
AR.Res Statistics Cr
Signal: Reset all statistic AR counters: Total number of AR, successful and unsuccessful no of AR.
AR.Res Service Cr
Signal: Reset the Service Counters for pickup and blocking
AR.Reset Lockout
Signal: The AR Lockout has been reset via the panel.
AR.Res Max Shots / h
Signal: The Counter for the maximum allowed shots per hour has been reset.
AR.ExBlo1-I
Module Input State: External Blocking1
AR.ExBlo2-I
Module Input State: External Blocking2
AR.Ex Shot Inc-I
Module input state: The AR Shot counter will be incremented by this external Signal. This can be used for
Zone Coordination (of upstream Auto Reclosure devices). Note: This parameter enables the functionallity
only. The assignment has to be set within the global parameters.
AR.Ex Lock-I
Module input state: External AR lockout.
AR.DI Reset Ex Lock-I
Module input state: Resetting the lockout state of the AR (if the resetting via digital inputs has been selected).
AR.Comm Reset Ex Lock-I
Module input state: Resetting the Lockout State of the AR by Communication.
AR.Abort: 1
Abort the AR-cycle, if the state of the assigned signal is true. If the state of this function is true the AR will be
aborted.
AR.Abort: 2
Abort the AR-cycle, if the state of the assigned signal is true. If the state of this function is true the AR will be
aborted.
AR.Abort: 3
Abort the AR-cycle, if the state of the assigned signal is true. If the state of this function is true the AR will be
aborted.
AR.Abort: 4
Abort the AR-cycle, if the state of the assigned signal is true. If the state of this function is true the AR will be
aborted.
AR.Abort: 5
Abort the AR-cycle, if the state of the assigned signal is true. If the state of this function is true the AR will be
aborted.
AR.Abort: 6
Abort the AR-cycle, if the state of the assigned signal is true. If the state of this function is true the AR will be
aborted.
Sync-check.Active
Signal: Active
Sync-check.ExBlo
Signal: External Blocking
Sync-check.LiveBus
Signal: Live-Bus flag: 1=Live-Bus, 0=Voltage is below the LiveBus threshold
Sync-check.LiveLine
Signal: Live Line flag: 1=Live-Line, 0=Voltage is below the LiveLine threshold
Sync-
check.SynchronRunTiming
Signal: SynchronRunTiming
Sync-check.SynchronFailed
Signal: This signal indicates a failed synchronization. It is set for 5s when the breaker is still open after the
Synchron-Run-timer has timed out.
Sync-check.SyncOverridden
Signal:Synchronizm Check is overridden because one of the Synchronizm overriding conditions (DB/DL or
ExtBypass) is met.
Sync-check.VDiffTooHigh
Signal: Voltage difference between bus and line too high.
Sync-check.SlipTooHigh
Signal: Frequency difference (slip frequency) between bus and line voltages too high.
Sync-check.AngleDiffTooHigh
Signal: Phase Angle difference between bus and line voltages too high.
Sync-check.Sys-in-Sync
Signal: Bus and line voltages are in synchronizm according to the system synchronizm criteria.
Sync-check.In-Sync Allowed
Signal: In-Sync Allowed