Safety Relays from IDEM           SCR-7 

H04 

Ver. A 

E61-329-00 

 

• 

2 start behavior possible: 

  -  Monitored manual start 

  -  Automatic start 

• 

Up to PL e, SILCL 3, category 4 

• 

STOP-category: 0 

 

• 

It is not allowed to open the device, tamper with the de-
vice or bypass the safety devices. 

• 

All relevant safety regulations and standards are to be 
observed. 

• 

The overall concept of the control system in which the 
device is incorporated must be validated by the user. 

• 

Failure to observe the safety regulations can result in 
death, serious injury and serious damage. 

Correct Use 

The SCR-7 is a universal emergency stop safety switching device 
with seven safe relay outputs that can quickly and safely stop the 
moving parts of a machine or system in case of danger.  

Applications  for  the  SCR-7  include  single  or  dual-channel 
emergency stop circuits and guard monitoring on machines and 
systems.  This  safety  relay  can  be  delivered  with  fixed  screw 
terminals or plug-in terminals. 

Features 

• 

7 safe, redundant relay outputs 

• 

4 auxiliary relay outputs; 2 auxiliary transistor outputs

 

• 

Connection of: 

    -  Emergency stop buttons 
    -  Safety switches 
    -  Non-contact safety switches 
    -  OSSD-Outputs 

• 

Single or dual-channel operation possible 

• 

Feedback loop for monitoring downstream contactors or 
expansion modules 

• 

Cyclical monitoring of the output contacts 

• 

Indication of the swiching state via LED 

 

Function 

The  emergency  stop  safety  switching  device  SCR-7  is 
designed for safe isolation of safety circuits according to EN 
60204-1  and  can  be  used  up  to  safety  category  4,  PL  e 
according to EN ISO 13849-1. 

The internal logical system closes the safety contacts when 
the start button is pressed. 

If  the  safety  switch  is  opened,  the  positively  driven  safety 
contacts are opened and safely switch the machine off. It is 
ensured  that  a  single  fault  does  not  lead  to  a  loss  of  the 
safety  function  and  that  every  fault  is  detected  by  cyclical 
self-monitoring  no  later  than  when  the  system  is  switched 
off and switched on again. 

The operating status of the device is indicate by the auxilia-
ry transistor outputs O1 and O2. 

O1: Ready. PWR is connected. 

O2: Both relay channel K1, K2 are switched on. 

Electrical 
Connection 

• 

A safety transformer according to IEC 61558-2-6 or a 
power supply unit with electrical isolation from the mains 
must be connected. 

• 

External fusing of the safety contacts (10 A gG) must be 
provided. 

• 

A maximum length of the control lines of 1000 meters 
with a line cross section of 0.75 mm

2

 must not be ex-

ceeded. 

• 

The line cross section must not exceed 2.5 mm

2

• 

If the device does not function after commissioning, it 
must be returned to the manufacturer unopened. Ope-
ning the device will void the warranty. 

Installation 

As per EN 60204-1, the device is intended for installation in 
control  cabinets  with  a  minimum  degree  of  protection  of 
IP54.  It  is  mounted  on  a  35-mm  DIN  rail  according  to                
DIN EN 60715 TH35. 

Safety 
Precautions 

• 

Installation and commissioning of the device must be 
performed only by authorized personnel

• 

Observe the country-specific regulations when installing 
the device. 

• 

The electrical connection of the device is only allowed to 
be made with the device isolated. 

• 

The wiring of the device must comply with the instruc-
tions in this user information, otherwise there is a risk 
that the safety function will be lost. 

Fig. 1 Block diagramm SCR-7 

Fig. 2  Installation / removal 

Fig. 3  Connections 

A1:  

Power Supply 

A2 : 

Power Supplay 

S11:  

DC 24V control voltage 

S10:  

Control line 

S12: 

Control line 

S13: 

Control line 

S14: 

Control line 

S21: 

Start, Control line 

O1;O2:

 

Aux transistor outputs 

0V: 

Reference common O1, O2 

81-82: 

Auxiliary Contact 

91-92: 

Auxiliary Contact 

101-102:  Auxiliary Contact 

101-112:  Auxiliary Contact 

13-14 bis 73-74: 

 

 

Safety Out1-7 