background image

TIME RELAY PCM-11 

USER MANUAL

ZAMEL 

sp. z o.o.

ul. Zielona 27, 43-200 Pszczyna, Poland

Tel. +48 32 210 46 65, Fax +48 32 210 80 04

www.zamel.com

, e-mail: [email protected]

plik: pcm-11_inst_ext_gb | modyfikacja: 24.09.2019

APPEARANCE

RA

NG

2

TI

M

1

RA

NG

1

TI

M

2

PCM-11

Connect this product to a 

single-phase power system 

according to applicable electri-

cal and safety standards and 

regulations. See this Manual 

for the wiring instructions. In-

stallation,  wiring  and  adjust-

ment/setting  shall  only  be  done  by  qualified 

electricians who have read and understood this 

User Manual and the functions of the product. 

Do not open or otherwise disassemble the prod-

uct housing; otherwise the product warranty will 

be void and an electrocution hazard may occur. 

Prior to installing and wiring this product, make 

sure that the wiring to be connected is not live. 

The conditions and methods of transport, stor-

age and operation of this product may affect its 

performance. Do not install the product if any of 

its components are missing, the product is dam-

aged or deformed in any way. If any malfunctions 

are found, consult the manufacturer.

CAUTION

FEATURES

TECHNICAL DATA

DESCRIPTION

●  Independent  switch  on  and  off  time 

settings.

●  A wide time setting range: from 0.1 s 

to 10 days.

●  Can generate pulse of specific dura-

tion.

●  Continuous on/off functions.

●  Relay  output:  one  16 A  max.  switch-

able contact.

●  Single-module housing.

●  DIN-Rail mountable.

PCM-11 is a multi-functional time 

relay for timer-based automatic control. 

The product can cyclically switch the 

wired system on for a preset time t1 and 

off for a preset time t2. The product can 

also switch the wired system on and off 

with a preset delay and generate pulses 

of specific duration. Key benefits include 

a very wide range of time settings, and 

the product can be switched on or off 

continuously. The operating mode can 

be switched to a different one before it 

ends.

PCM-11

Power input terminals: L; N

Rated supply voltage: 230 V AC

Supply voltage tolerance: -15 ÷ +10 %

Rated mains frequency: 50 / 60 Hz

Rated current load: 10 mA

Time t setting range: 0.1 s ÷ 10 days (in increments or stepless)

Time measurement accuracy: ± 3 s / 24h max. at 25 ºC

Relay contact ratings: 1NO/NC-16 A/250 V AC1 4000 VA

Wiring terminals: 5

Wiring size: 0.2 ÷ 2.50 mm²

Operating temperature: -10 ÷ +55 ºC

Installation orientation: any

Housing mounting: DIN-Rail

Housing protection rating: IP20

Overvoltage category: II

Pollution class: 2

Surge voltage: 2 kV

Dimensions: single module (17.5 mm) 90x17.5x66 mm

Weight: 0.076 kg

Relay output terminals
(12, 11, 14)

Time t1  range selection

Time t2 range selection

Stepless time t1 setting

Stepless time t2 setting

Do not dispose of this device with other 

waste! In order to avoid harmful effects 

on the environment and human health, 

the used device should be stored in 

designated areas. For this purpose, you 

can dispose of household waste free of 

charge and in any quantity to a collection 

point set up, as well as to the shop when 

you buy new equipment.

Power input terminals