Q   R E L A Y ( s i n g l e - p h a s e )   I N S T A L L A T I O N

PREPARATION

In Enphase installations, the single-phase Q Relay (network system relay 

controller) acts as a galvanic disconnection device. It is designed for single 

phase use and has built in contactors. During specified grid abnormalities, 

the Q Relay disconnects the Enphase Microinverters from the AC grid, and 

when the voltages return to normal and the grid frequency is in the accept-

able range, the Q Relay reconnects the microinverters to the AC grid. The 

Q Relay has built in current sensing that can detect DC current injection 

required by VDE V 0126-1-1 requirements.
The Q Relay works together with the Envoy-S to meet the need to 

break both line and neutral per grid requirements. See full installation 

instructions for the Enphase Envoy-S and/or Enphase Microinverters at: 

enphase.com/support

It is best practice to install the Q Relay when installing the Envoy-S and 

before commissioning the system. 
The Q relay is IP-20 rated. You must mount it in an environmentally pro-

tected enclosure. Typically this is a switchboard.

SAFETY

IMPORTANT SAFETY INSTRUCTIONS.  

SAVE THIS INFORMATION.

 

Follow all safety and assembly instructions when installing the 

Q Relay. 

Safety Instructions

+

DANGER

: Risk of electric shock. Risk of fire. Do not 

attempt to repair the Q Relay; it contains no user-ser-

viceable parts. Tampering with or opening the Q Relay 

will void the warranty. Warranty void if cover removed. If 

the Q Relay fails, contact Enphase Customer Support for 

assistance (

http://enphase.com/global/contact/

). 

+

DANGER

: Risk of electric shock. Always open or discon-

nect circuit from power-distribution system (or service) of 

building before installing or servicing the Q Relay.

+

DANGER

: Risk of electric shock. Do not use Enphase 

equipment in a manner not specified by the manufac-

turer. Doing so may cause death or injury to persons, or 

damage to equipment. 

+

DANGER

: Risk of electric shock. Be aware that installa-

tion of this equipment includes risk of electric shock. If 

you wire the Q Relay at the sub-board, always de-energise 

the sub-board before beginning.

+

DANGER

: Risk of electric shock. Risk of fire. Only qualified 

personnel should troubleshoot, install, or replace the Q 

Relay.

*

WARNING

: Before installing or using the Q Relay, read 

all instructions and cautionary markings in the technical 

description and on the Q Relay.

*

WARNING

: Risk of equipment damage. When installing 

the Q Relay in an enclosure, choose an area for installa-

tion where ambient temperature remains between -40º 

C and 50º C.  

NOTE

: Perform all electrical installations in accordance 

with all national and local electrical codes.

NOTE

: Install a residual current circuit breaker if required 

by national regulations.

NOTE

: To ensure optimal reliability and to meet warranty 

requirements, the Enphase Q Relay must be installed 

according to the instructions in this guide.

A

Hz

Q RELAY

TEST

B

C

D

I1●

I1

I2●

I2

I3●

I3 

I1●

I1

I2●

I2

I3●

I3

1 / 5 2 / 6 3 / 7 4 / 8

NO

RefGen Com / DRM Ø

C

Production

Consumption

Digital Input

Relay

PD, B300

OVC II

 

CU, 2.5 mm

2

, 75C

MEAS CAT III

OVC III

L1

L2

L3

N

0   1   2   3   4   5   6   7  8

AU/NZ: DRM Port

N: blue

L: brown

LED1
LED2

Enphase Energy, 1420 N. McDowell Blvd, Petaluma, CA 94954 USA
© 2018 Enphase Energy. All rights reserved.

 

Enphase Customer Support: enphase.com/en-us/support/contact

INSTALLATION

DANGER! Risk of electric shock. Always de-energise circuits before   

  beginning wiring.

A )  Install the Enphase Envoy-S as directed in steps 1 - 4 of the 

Envoy-S Quick 

Install Guide

.

B )  Install the Q Relay in a protected environment (e.g., switchboard) on a 

35 mm DIN rail near the Envoy-S.

C )  Connect the Line and Neutral conductors from the PV system to the 

lower terminals of the Q Relay so that the Neutral is on the left terminal 

and the Line is on the right terminal. 

D )  Connect a Neutral conductor from the upper left terminal of the Q Relay 

to the Neutral busbar.

E )  Connect a Line conductor from the upper right terminal of the Q Relay to 

an IEC/AS/NZS 60947-2 approved circuit breaker rated for no more than 

20A. The circuit breaker must be suitably located and easily reached. It 

must also be marked as the disconnecting device for the PV system.

F )  Energise the circuit.
G )  Upon power up, the LEDs should both turn green to indicate the AC 

voltage and frequency are within specification of the grid code. See the 

LED states table.

H )  Use the Enphase Installer Toolkit to send a grid profile to the Q Relay and 

microinverters as directed in Step 5 of the 

Envoy-S Quick Install Guide

.

LED States

LED # 1

(voltage)

LED # 2

(Hz, DCI)

Description

Condition

Relay

OFF

OFF

AC on terminals too low 

Unpowered; 

non-functional

OPEN

GREEN 

(solid)

X

Phase voltage within range

--

--

RED  

(solid)

X

One or more voltage setpoints 

has timed out or reconnection 

value not met

Fault

OPEN

GREEN 

(solid)

GREEN 

(solid)

Voltage, frequency within range 

& DCI, if used, is below fault 

levels

Normal

CLOSED

X

GREEN 

(solid)

Line frequency (and DCI, if 

used)are within limits

--

--

X

RED  

(solid)

Grid frequency timed out or 

reconnection  value  not met

Fault

OPEN

RED  

(flashing)

RED  

(flashing)

No profile set; device not 

configured

Fault

OPEN

RED  

(solid)

RED  

(solid)

Test button in use

Test  

contactor

toggle 

state

Wiring Diagram

Specifications

Over voltage category

III

Pollution degree

2

Operating AC voltage range for power 

supply

230 to 240 Vrms

Nominal input frequency

50 Hz

Voltage and frequency acquisition time 

on valid input during normal operation

100 ms (5 line cycles @ 50Hz)

Output

2-pole normally open relay (L1 and N)

Output power rating

4.8 kVA

Output rating (typical)

230 to 240 VAC, 20A

Power consumption

10 VA

Conducted and radiated EMI

IEC 61326-1, BS EN 61000-3-2, BS EN 61000-

3-3, BS EN 50065-1, BS EN 50065-2-2

Operating temperature range

-40 °C to 50 °C

IP rating

IP 20 (must be in protected environment)

Relative humidity

0 to 95 non-condensing

Compliance

IEC 61010

 Key:

 

A

: Output from system

 

B

: From grid

 

C

: Envoy-S terminal block

 

D

: Switchboard

Summary of Contents for Q Relay

Page 1: ...o the instructions in this guide A Hz Q RELAY TEST B C D I1 I1 I2 I2 I3 I3 I1 I1 I2 I2 I3 I3 1 5 2 6 3 7 4 8 NO RefGen Com DRM Ø C Production Consumption Digital Input Relay PD B300 OVC II CU 2 5 mm2 75C MEAS CAT III OVC III L1 L2 L3 N 0 1 2 3 4 5 6 7 8 AU NZ DRM Port N blue L brown LED1 LED2 Enphase Energy 1420 N McDowell Blvd Petaluma CA 94954 USA 2018 Enphase Energy All rights reserved Enphase ...

Page 2: ...I2 I3 I3 I1 I1 I2 I2 I3 I3 1 5 2 6 3 7 4 8 NO RefGen Com DRM Ø C Production Consumption Digital Input Relay PD B300 OVC II CU 2 5 mm2 75C MEAS CAT III OVC III L1 L2 L3 N 0 1 2 3 4 5 6 7 8 AU NZ DRM Port N blue L brown LED1 LED2 EnphaseEnergy 1420N McDowellBlvd Petaluma CA94954 États Unis 2018 Enphase Energy Tous droits réservés Assistance clientèle Enphase enphase com fr fr support contact INSTALL...

Page 3: ... B C D I1 I1 I2 I2 I3 I3 I1 I1 I2 I2 I3 I3 1 5 2 6 3 7 4 8 NO RefGen Com DRM Ø C Production Consumption Digital Input Relay PD B300 OVC II CU 2 5 mm2 75C MEAS CAT III OVC III L1 L2 L3 N 0 1 2 3 4 5 6 7 8 AU NZ DRM Port N blue L brown LED1 LED2 Enphase Energy 1420 N McDowell Blvd Petaluma CA 94954 USA 2018 Enphase Energy Alle Rechte vorbehalten Enphase Kundensupport enphase com en us support contac...

Page 4: ... de garantievereisten A Hz Q RELAY TEST B C D I1 I1 I2 I2 I3 I3 I1 I1 I2 I2 I3 I3 1 5 2 6 3 7 4 8 NO RefGen Com DRM Ø C Production Consumption Digital Input Relay PD B300 OVC II CU 2 5 mm2 75C MEAS CAT III OVC III L1 L2 L3 N 0 1 2 3 4 5 6 7 8 AU NZ DRM Port N blue L brown LED1 LED2 Enphase Energy 1420 N McDowell Blvd Petaluma CA 94954 VS 2018 Enphase Energy Alle rechten voorbehouden Enphase klante...

Reviews: