background image

 

 

 Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. England 

Telephone: +44 (0) 1902 773746 Facsimile: +44 (0) 1902 420639 Email: [email protected] Web: http://www.broycecontrol.com

 

The information provided in this literature is believed to be accurate (subject to change without prior notice); however, use of such information shall be entirely at the user’s own risk. 

 

 

ELRV30-2-A RMS 

012366 Page 1 of 2 

 

 

CONNECTION DIAGRAM

 

 

14

1

standard

output

positive safety

output

te

s

t

re

s

e

t

A1 (+ve)

A2 (-ve)

Fault level output*

(i.e. lamp)

2

3

5

7

9

11 13

4

6

8

10 12

toroid

5

0

m

m

a

x

.

50m* max.

L1

L2

L3

N

E

Note: The voltage 
across the fault level 
output MUST NOT 
exceed 240V~ (For 
400V~ units used in 
3-Phase installations, 
connect the load between 
terminal 2 and neutral)

The Earth MUST NOT pass through
the toroid.
For single phase applications, only the live
and neutral need to be passed through the
toroid. 
*Cabling:
For distances >1m, use twisted pair cable between 
the unit and toroid. Always ensure cables to toroid 
and remote test / reset switches ARE KEPT AWAY 
from mains and data cables in the same installation.

Both relays are shown 
in the de-energised state
(i.e. where power is not 
present on terminals 1 and 3)

E

* Only available on AC supply models

 

 

 

 

 
 

 

 

Type: ELRV-30 

True RMS Earth Leakage Relay (Variable) - Type A 

 

q

 

70mm DIN rail housing 

q

 

Designed to monitor and detect true RMS, earth fault currents (up to 30A) in conjunction with a separate toroid 

q

 

Fast response time of <25mS

to fault currents that are 5 x greater than the set trip current 

q

 

Digital LED Display shows measured leakage current, various user settings and diagnostics 

q

 

Microprocessor controlled with internal monitoring (self-checking) 

q

 

Sensitivity (I

n) and time delay (

t) adjustable using simple 2-button operation 

q

 

“Display” push button allows user to view settings without needing to open the tamperproof cover. The “last recorded” peak 
trip current can also be recalled using the same push button 

q

 

Single button operation for “Test / Reset” and connection facility for remote “Test” and “Reset” push buttons 

q

 

Connection for remote lamp facility warning user prior to a trip condition (level adjustable by user) 

q

 

Toroid open and short circuit detection (unit forced to trip during open circuit condition) 

q

 

2 x SPDT relay output 8A. LED indication of user settings / fault condition after unit has tripped  

1

 “inst.” time delay setting / fault current <30A

 

 

 

 
 
 

 

 

 

 

 

 

 

 

                                                                                                                                                                                                                                                                                                             
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Dims: 

to DIN 43880 

W. 70mm 

 

TECHNICAL SPECIFICATION 

 

Supply voltage Un (1, 3): 

12 – 60V DC (85 – 115% of U) 

 

 

24, 115, 230, 400V AC (85 – 115% of Un) 
Galvanic isolation between the supply and the toroid and 

remote test / reset connections on AC supply versions. 

Supply frequency: 

50/60/400Hz (AC supplies) 

Isolation: 

 

Over voltage cat. III  

Rated impulse  

 withstand voltage: 

 

(1.2 / 50

µ

S) IEC 60664  

800V (24V AC supply 

 

 

2.5kV (115V AC supply)  

 

 

4kV (230V, 400V AC supplies) 

Power consumption (max.): 6VA (AC supplies), 5W (DC supply)

 

 

Monitored leakage current:  2mA to 30A (50/60/400Hz)(through external toroid with 

1000:1 ratio and connected to terminals 11 and 13) 

 

Sensitivity I

n:  

6, 10, 30, 50, 75, 100, 300, 500, 750mA 

 

 

1, 3, 5, 7.5, 10, 15, 20, 25, 30A (user selectable) 

Trip level: 

 

75% of I

n (nominal) 

Hysteresis:   

8% of I

n or 2mA, whichever greater 

Accuracy: 

±

15% (valid range 10 …. 110% of I

n or 2mA, 

whichever greater) 

Time delay 

t: 

inst., 50, 250, 500mS, 1, 2.5, 5, 10 sec. (user selectable) 

  

Note: For I

n settings of 30mA or less, the time delay is fixed 

to inst. (instantaneous, <25mS) and is not adjustable. 

 

Measured current: 

Displayed on auto ranging 2 digit 7-segment red LED display

 

Display Resolution: 

100uA min. 

Reset time: 

<200mS (from supply interruption) 

 

Power on delays: 

Self test duration: <5 secs.  

(from application of supply  Delay before P.S.O. relay energises “td”: 600mS (Note: relay  
to terminals 1 and 3) 

will energise during self test period assuming no fault present)

 

 

Memory: 

storage of the leakage fault and reset with “test / reset” button 

 

Ambient temp: 

-5 to +60

°

 

 

-5 to +40

°

C (in accordance with IEC 755) 

Relative humidity: 

+95% 

 

Output : 

 

2 x SPDT relay (4, 6, 8 / 10, 12, 14) 

Output rating:  

AC1 

250V 8A (2000VA) 

 

 

AC15 

250V 2.5A 

 

 

DC1 

25V 8A (200W) 

Electrical life:   

 150,000 ops at rated load 

Dielectric voltage: 

2kV AC (rms) IEC 60947-1 

Rated impluse 
 withstand voltage: 

4kV (1.2 / 50

µ

S) IEC 60664 

 

Remote “test” / “reset” 

(5, 7, 9) 

Requires two N.O. contacts. (i.e. push buttons) 

Contact closure time: 

>100mS 

 

Fault level output (1, 2): 

50% of I

n (factory set) 

User adjustable from 10 - 65% in 5% increments 

Hysteresis:   

8% of I

n or 2mA, whichever greater 

Load (resistive): 

40mA max. @ 240V 

Note: A remote lamp can only be connected when terminals 1 
and 3 are being supplied with an AC supply

 

 

Housing: 

 

Grey flame retardant Lexan UL94 VO 

Weight: 

 

 250g (AC supplies), 

 170g (DC supply) 

Mounting option: 

On to 35mm symmetric DIN rail to BS5584:1978  
(EN50 002, DIN 46277-3)  

Terminal conductor size: 

 2.5mm

2

 stranded. 

 4mm

2

 solid 

 

Approvals: 

 

Conforms to: IEC 755. IEC 61543 (EMC) 
Radiated Immunity: IEC 61000-4-3: 1.89GHz @ 30V/m 

 and 

 pending. 

CE

 and       Compliant.

 

 

Options 

For other supply voltages, alternative trip levels or time delays, please consult the sales office. 

 

Accessories – Toroids 

 

Toroid Type: 

Internal diameter: 

I

n (min.) A 

BZCT035 

35mm 

 

0.03 

BZCT070 

70mm 

 

0.03 

BZCT120 

120mm 

 

0.1 

BZCT210 

210mm 

 

0.3 

Note:

 

( ) Numbers in brackets shown above refer to terminal numbers on the relay housing. 

 

FUNCTION DIAGRAM

 

Standard

output

fault

current

failure of connection 

to toroid

"reset"

"test"

supply

interrupted

Trip level (I n)

Positive safety

output

t

(combined test/reset button pressed)

Reset level

td

td

Terminal Protection to IP20 

 

INSTALLATION

 

 

 

BEFORE INSTALLATION, ISOLATE THE SUPPLY.

 

 

Connect the unit as shown in the diagram below (N.B. certain features may not be required and 
therefore do not need to be connected). 

 

Operational and setting information can be found on the reverse of this data sheet. 

 

This unit should be installed in conjunction with the latest wiring regulations and practices (IEE, etc)

 

 

 

 

MOUNTING DETAILS

 

 

Insert screwdriver

to release clip

4

9

.5

3

3

6

3

.5

45

85

 

 

 

Installation work must be carried

out by qualified personnel.

Please state Supply 

voltage when ordering.

 

Reviews: