Page 5-37
IL17569
Effective June, 2001
5.5.2.7 Breaker Failure
50BF Bkr Config
This is the 50BF device Breaker Failure Configuration setting. The
50BF Bkr Config sets the conditions for the FP-5000 to detect a
breaker failure condition. This function is only activated after initiation.
The four 50BF Bkr Config setting descriptions are shown below:
50BF Bkr Config
The 50BF device is turned off, so no
set to Off:
breaker failure can be detected
internally or externally.
50BF Bkr Config
The 50BF function will be initiated by
set to Internal:
an internal trip signal.
50BF Bkr Config
The 50BF function will be initiated by
set to External:
an external signal.
50BF Bkr Config
The 50BF function will be initiated by
set to Both:
either an internal or external trip
signal.
50BF Bkr Failure:
This includes the 50BF device
Breaker Failure setting, which is only
applied if the 50BF Bkr Config setting
is not set to “off.” The default
configuration for the output logic
maps the Breaker Failure trip (i.e.
Breaker State Lockout) to output
Relay 3 so that a separate lockout
relay (device 86) can be used to
provide backup tripping. The breaker
failure function continues to monitor
all phase currents after a trip is
initiated by ether the FP-5000 or an
external device. The breaker failure
trip output operates if the phase or
ground currents do not drop below the
programmed I Ph (pu) or I Gnd (pu)
setting levels within the breaker
failure Delay time setting.
Figure 5-2. Breaker Failure Logic Diagram
The I Ph (pu) is an independent overcurrent
element monitoring the phase currents. It is
recommended to set the level above maximum
load currents even though the Breaker failure
logic is only initiated upon a breaker trip signal.
The I Gnd (pu) is an independent ground
overcurrent element that uses both the
measured residual ground current (Ir) and the
measured ground current (Ix). It is recom-
mended to be set above any normal or
expected rms ground currents.
Summary of Contents for Cutler-Hammer FP-5000
Page 1: ...IL17569 Effective June 2001 Instructions for FP 5000 Protective Relay...
Page 7: ...IL17569 Table of Contents 6 Effective June 2001 This page left blank intentionally...
Page 13: ...IL17569 Page 2 2 Effective June 2001 Figure 2 2 FP 5000 Simple Wye Connected Application...
Page 14: ...Page 2 3 IL17569 Effective June 2001 Figure 2 3 FP 5000 Simple Open Delta Application...
Page 19: ...IL17569 Page 2 8 Effective June 2001 This page left blank intentionally...
Page 25: ...IL17569 Page 3 6 Effective June 2001 This page left blank intentionally...
Page 98: ...IL17569 Page 5 50 Effective June 2001 This page left blank intentionally...
Page 108: ...IL17569 Page 6 10 Effective June 2001 Figure 6 10 Common Ct Wiring Configurations...
Page 141: ...IL17569 Page 11 4 Effective June 2001 This page left blank intentionally...
Page 165: ...IL17569 Page Appendix 6 Effective June 2001 Figure 13 2 ANSI Very Inverse...
Page 166: ...Page Appendix 7 IL17569 Effective June 2001 Figure 13 3 ANSI Extremely Inverse...
Page 167: ...IL17569 Page Appendix 8 Effective June 2001 Figure 13 4 IEC A Figure 13 4 IEC A...
Page 168: ...Page Appendix 9 IL17569 Effective June 2001 Figure 13 5 IEC B...
Page 169: ...IL17569 Page Appendix 10 Effective June 2001 Figure 13 6 IEC C...
Page 170: ...Page Appendix 11 IL17569 Effective June 2001 Figure 13 7 IEC...
Page 171: ...IL17569 Page Appendix 12 Effective June 2001 Figure 13 8 ANSI...
Page 172: ...Page Appendix 13 IL17569 Effective June 2001 Figure 13 9 Thermal...
Page 173: ...IL17569 Page Appendix 14 Effective June 2001 Figure 13 10 Phase I4 t...
Page 174: ...Page Appendix 15 IL17569 Effective June 2001 Figure 13 11 Phase I2 t...
Page 175: ...IL17569 Page Appendix 16 Effective June 2001 Figure 13 12 Phase It...
Page 176: ...Page Appendix 17 IL17569 Effective June 2001 Figure 13 13 Phase 12 I4 t...
Page 177: ...IL17569 Page Appendix 18 Effective June 2001 Figure 13 14 Phase I2 t...
Page 178: ...Page Appendix 19 IL17569 Effective June 2001 Figure 13 15 Ground IT...
Page 180: ...Page Appendix 21 IL17569 Effective June 2001 This page left blank intentionally...
Page 187: ...Publication No IL17569 June 2001 Pittsburgh Pennsylvania U S A...