Page 5-15
IL17569
Effective June, 2001
Table 5.4 Logging Settings
Phase time overcurrent (51P) and instantaneous (50P-1 & 50P-2) device settings
Display Setting
Description
Setpoint Range/
Default
Selected
Refer to
Value Selection
Setting
Value
Sec. #
Current Demand
Current Demand Logging Setting
5.5.4
Interval (m):
Select interval for taking current
1 to 60 minutes
15
5.5.4
demand measurement
(increments of 1)
in minutes
Power Demand
Power Demand Logging Setting
5.5.4
Window:
Select type of power
Fixed or Slide
Fixed
5.5.4
demand window
Interval (m):
Select interval for taking power
1 to 60 minutes
15
5.5.4
demand measurement
(increments of 1)
in minutes
Event Log
Event Log Settings for Pickups,
5.5.4
Enable
Contact Inputs,
12.2.1
and Communications
I Pickup:
Select I Pickup to be logged
No or Yes
Yes
V Pickup:
Select V Pickup to be logged
No or Yes
No
Freq Pickup:
Select Freq Pickup to be logged
No or Yes
No
PF Pickup:
Select PF Pickup to be logged
No or Yes
No
Unbal Pickup:
Select Unbal Pickup to be logged
No or Yes
No
SYSALM Pickup:
Set system alarm pickup
No or Yes
No
to be logged
Cin 1:
Set Cin 1 event to be logged
No or Yes
No
Cin 2:
Set Cin 2 event to be logged
No or Yes
No
Cin 3:
Set Cin 3 event to be logged
No or Yes
No
Cin 4:
Set Cin 4 event to be logged
No or Yes
No
Cin 5:
Set Cin 5 event to be logged
No or Yes
No
Cin 6:
Set Cin 6 event to be logged
No or Yes
No
Cin 7:
Set Cin 7 event to be logged
No or Yes
No
Cin 8:
Set Cin 8 event to be logged
No or Yes
No
Comm.:
Set Comm event to be logged
No or Yes
No
Summary of Contents for Cutler-Hammer FP-5000
Page 1: ...IL17569 Effective June 2001 Instructions for FP 5000 Protective Relay...
Page 7: ...IL17569 Table of Contents 6 Effective June 2001 This page left blank intentionally...
Page 13: ...IL17569 Page 2 2 Effective June 2001 Figure 2 2 FP 5000 Simple Wye Connected Application...
Page 14: ...Page 2 3 IL17569 Effective June 2001 Figure 2 3 FP 5000 Simple Open Delta Application...
Page 19: ...IL17569 Page 2 8 Effective June 2001 This page left blank intentionally...
Page 25: ...IL17569 Page 3 6 Effective June 2001 This page left blank intentionally...
Page 98: ...IL17569 Page 5 50 Effective June 2001 This page left blank intentionally...
Page 108: ...IL17569 Page 6 10 Effective June 2001 Figure 6 10 Common Ct Wiring Configurations...
Page 141: ...IL17569 Page 11 4 Effective June 2001 This page left blank intentionally...
Page 165: ...IL17569 Page Appendix 6 Effective June 2001 Figure 13 2 ANSI Very Inverse...
Page 166: ...Page Appendix 7 IL17569 Effective June 2001 Figure 13 3 ANSI Extremely Inverse...
Page 167: ...IL17569 Page Appendix 8 Effective June 2001 Figure 13 4 IEC A Figure 13 4 IEC A...
Page 168: ...Page Appendix 9 IL17569 Effective June 2001 Figure 13 5 IEC B...
Page 169: ...IL17569 Page Appendix 10 Effective June 2001 Figure 13 6 IEC C...
Page 170: ...Page Appendix 11 IL17569 Effective June 2001 Figure 13 7 IEC...
Page 171: ...IL17569 Page Appendix 12 Effective June 2001 Figure 13 8 ANSI...
Page 172: ...Page Appendix 13 IL17569 Effective June 2001 Figure 13 9 Thermal...
Page 173: ...IL17569 Page Appendix 14 Effective June 2001 Figure 13 10 Phase I4 t...
Page 174: ...Page Appendix 15 IL17569 Effective June 2001 Figure 13 11 Phase I2 t...
Page 175: ...IL17569 Page Appendix 16 Effective June 2001 Figure 13 12 Phase It...
Page 176: ...Page Appendix 17 IL17569 Effective June 2001 Figure 13 13 Phase 12 I4 t...
Page 177: ...IL17569 Page Appendix 18 Effective June 2001 Figure 13 14 Phase I2 t...
Page 178: ...Page Appendix 19 IL17569 Effective June 2001 Figure 13 15 Ground IT...
Page 180: ...Page Appendix 21 IL17569 Effective June 2001 This page left blank intentionally...
Page 187: ...Publication No IL17569 June 2001 Pittsburgh Pennsylvania U S A...