Page 5-3
IL17569
Effective June, 2001
5.3 FP-5000 Setting Table
NOTE: All voltage settings are in secondary units. All current settings are in per unit. All System settings are in primary units. Time delay
setting is in cycles (c), seconds (s), or minutes (m).
Program Date:
Control Schematic:
FP-5000 Relay ID:
Breaker ID:
Work Order #:
Line Protected:
Table 5.1 System Config
Display Setting
Description
Setpoint Range/
Default
Selected
Refer to
Value Selection
Setting
Value
Sec. #
Frequency:
Nominal system
50 Hz or 60 Hz
60
5.5.1
operating frequency
Phase Seq:
Nominal system phase
ABC or ACB
ABC
5.5.1
sequence or rotation
Ct Connect:
Ct connect determines how
3-wire, 4Ct In, 4Ct Ig
3-wire
5.5.1
residual current IR is calculated
8.2
3-wire: 4th Ct is independent
4Ct In: 4-wire system with
4th Ct on neutral conductor
4Ct Ig: 4-wire system with
4th Ct on ground conductor
PH Ct Ratio:
Ct ratio of the phase
I
nom
to 6000
500:I
nom
3
5.5.1
current Cts
(Increments of I
nom
)
IX Ct Ratio:
Ct ratio of the fourth Ct
I
nom
to 6000
500:I
nom
3
5.5.1
(Increments of I
nom
)
VT Connect:
Voltage transformer
Wye or Delta
Wye
5.5.1
connection
6.3.2
Main VTR:
Main voltage
1 to 8000
100
5.5.1
transformer ratio:1
(Increments of 1)
Aux VTR:
Auxiliary voltage
1 to 8000
100
5.5.1
transformer ratio:1
(Increments of 1)
Prim Units:
Selection of primary or
Yes, No
No
5.5.1
secondary units of displayed
values
I/O Config:
Default input/output
Default or Custom
1
Default
5.5.1
configuration or customized
input/output
Prog Logic:
Default or custom
Default or Custom
1
Default
5.5.1
Programmable logic settings
Remote Set:
Enables or disables remote
Enable or disable
Enable
5.5.1
download setpoints capability
from rear communication port
Summary of Contents for Cutler-Hammer FP-5000
Page 1: ...IL17569 Effective June 2001 Instructions for FP 5000 Protective Relay...
Page 7: ...IL17569 Table of Contents 6 Effective June 2001 This page left blank intentionally...
Page 13: ...IL17569 Page 2 2 Effective June 2001 Figure 2 2 FP 5000 Simple Wye Connected Application...
Page 14: ...Page 2 3 IL17569 Effective June 2001 Figure 2 3 FP 5000 Simple Open Delta Application...
Page 19: ...IL17569 Page 2 8 Effective June 2001 This page left blank intentionally...
Page 25: ...IL17569 Page 3 6 Effective June 2001 This page left blank intentionally...
Page 98: ...IL17569 Page 5 50 Effective June 2001 This page left blank intentionally...
Page 108: ...IL17569 Page 6 10 Effective June 2001 Figure 6 10 Common Ct Wiring Configurations...
Page 141: ...IL17569 Page 11 4 Effective June 2001 This page left blank intentionally...
Page 165: ...IL17569 Page Appendix 6 Effective June 2001 Figure 13 2 ANSI Very Inverse...
Page 166: ...Page Appendix 7 IL17569 Effective June 2001 Figure 13 3 ANSI Extremely Inverse...
Page 167: ...IL17569 Page Appendix 8 Effective June 2001 Figure 13 4 IEC A Figure 13 4 IEC A...
Page 168: ...Page Appendix 9 IL17569 Effective June 2001 Figure 13 5 IEC B...
Page 169: ...IL17569 Page Appendix 10 Effective June 2001 Figure 13 6 IEC C...
Page 170: ...Page Appendix 11 IL17569 Effective June 2001 Figure 13 7 IEC...
Page 171: ...IL17569 Page Appendix 12 Effective June 2001 Figure 13 8 ANSI...
Page 172: ...Page Appendix 13 IL17569 Effective June 2001 Figure 13 9 Thermal...
Page 173: ...IL17569 Page Appendix 14 Effective June 2001 Figure 13 10 Phase I4 t...
Page 174: ...Page Appendix 15 IL17569 Effective June 2001 Figure 13 11 Phase I2 t...
Page 175: ...IL17569 Page Appendix 16 Effective June 2001 Figure 13 12 Phase It...
Page 176: ...Page Appendix 17 IL17569 Effective June 2001 Figure 13 13 Phase 12 I4 t...
Page 177: ...IL17569 Page Appendix 18 Effective June 2001 Figure 13 14 Phase I2 t...
Page 178: ...Page Appendix 19 IL17569 Effective June 2001 Figure 13 15 Ground IT...
Page 180: ...Page Appendix 21 IL17569 Effective June 2001 This page left blank intentionally...
Page 187: ...Publication No IL17569 June 2001 Pittsburgh Pennsylvania U S A...