Page 6-5
IL17569
Effective June, 2001
Figure 6-4. FP-5000 Outer Chassis Rear Connections
1
1
1
1
1
2
2
2
2
2
4
4
4
4
4
5
5
5
5
5
6
6
6
6
6
7
7
7
7
7
8
8
8
8
8
1
TB1
2
TB2
3
TB3
4
J1
5
J2
6
J3
7
J4
8
J5
9
Ct Receptical
*
Protective Earth
3
3
3
3
3
9
9
9
9
9
Reserved (TB2)
Terminals 211 and 212 are reserved for future design efforts. Do not
connect circuits to these terminals.
VT Terminals (TB2)
Pins 213–218 are phase A, B, C, Auxiliary and ground voltage
inputs from the VT (voltage transformer) module. The VT module is
used to measure the line voltage and steps down the voltage to a
smaller potential. It also provides isolation to the FP-5000 and from
the voltage bus.
Figure 6-8
and
Figure 6-9
show Delta and Wye
connected feeder protection, respectively.
Note:
Careful attention should be made to the phase wiring to
avoid erroneous power and voltage indications as well as
damage to the FP-5000.
Standard Communication Board TB3
There are three circuits on the “Standard communication” Terminal
Block assembly TB3:
• J1 INCOM PN – is the connection of a PowerNet INCOM twisted
pair communications interface. The connection is part of a daisy
chained multi-point twisted pair interface. J1-1 and J1-2 are for the
twisted pair connections and J1-3 for shield termination. The
removable terminal plug can facilitate debug of the INCOM
hardware interface. Switch selectable termination is located on the
communication board of the inner chassis and can be accessed
through an opening in the metal chassis with the draw-out
removed. It is shipped open. Refer to Section 10 for INCOM wiring
rules and details.
• J2 INCOM AB – this is an INCOM type interface reserved for
future design features. The hardware is identical to J1 accept that
there is a non-switch selectable 100 ohm termination resistor
built in.
• J3 Zone Interlock – This is the termination for both the zone
interlock Zone Out (J3-1) and Zone In (J3-4) circuits with duplicate
J3-2 and J3-5 Zone com. connections, for Zone signal returns.
The shield connection J3-3 is grounded to the chassis and is not
needed for noise immunity. Twisted pair control wiring of 14-18
AWG is recommended.
• J4 and J5 are unpopulated future design options.
It is recommended that the wires terminated at TB3 be fitted on the
end with ferrules to eliminate fray shorting and the cable stress
released by strapping them to the back of the draw-out panel near
the FP-5000.
*
*
*
*
*
Summary of Contents for Cutler-Hammer FP-5000
Page 1: ...IL17569 Effective June 2001 Instructions for FP 5000 Protective Relay...
Page 7: ...IL17569 Table of Contents 6 Effective June 2001 This page left blank intentionally...
Page 13: ...IL17569 Page 2 2 Effective June 2001 Figure 2 2 FP 5000 Simple Wye Connected Application...
Page 14: ...Page 2 3 IL17569 Effective June 2001 Figure 2 3 FP 5000 Simple Open Delta Application...
Page 19: ...IL17569 Page 2 8 Effective June 2001 This page left blank intentionally...
Page 25: ...IL17569 Page 3 6 Effective June 2001 This page left blank intentionally...
Page 98: ...IL17569 Page 5 50 Effective June 2001 This page left blank intentionally...
Page 108: ...IL17569 Page 6 10 Effective June 2001 Figure 6 10 Common Ct Wiring Configurations...
Page 141: ...IL17569 Page 11 4 Effective June 2001 This page left blank intentionally...
Page 165: ...IL17569 Page Appendix 6 Effective June 2001 Figure 13 2 ANSI Very Inverse...
Page 166: ...Page Appendix 7 IL17569 Effective June 2001 Figure 13 3 ANSI Extremely Inverse...
Page 167: ...IL17569 Page Appendix 8 Effective June 2001 Figure 13 4 IEC A Figure 13 4 IEC A...
Page 168: ...Page Appendix 9 IL17569 Effective June 2001 Figure 13 5 IEC B...
Page 169: ...IL17569 Page Appendix 10 Effective June 2001 Figure 13 6 IEC C...
Page 170: ...Page Appendix 11 IL17569 Effective June 2001 Figure 13 7 IEC...
Page 171: ...IL17569 Page Appendix 12 Effective June 2001 Figure 13 8 ANSI...
Page 172: ...Page Appendix 13 IL17569 Effective June 2001 Figure 13 9 Thermal...
Page 173: ...IL17569 Page Appendix 14 Effective June 2001 Figure 13 10 Phase I4 t...
Page 174: ...Page Appendix 15 IL17569 Effective June 2001 Figure 13 11 Phase I2 t...
Page 175: ...IL17569 Page Appendix 16 Effective June 2001 Figure 13 12 Phase It...
Page 176: ...Page Appendix 17 IL17569 Effective June 2001 Figure 13 13 Phase 12 I4 t...
Page 177: ...IL17569 Page Appendix 18 Effective June 2001 Figure 13 14 Phase I2 t...
Page 178: ...Page Appendix 19 IL17569 Effective June 2001 Figure 13 15 Ground IT...
Page 180: ...Page Appendix 21 IL17569 Effective June 2001 This page left blank intentionally...
Page 187: ...Publication No IL17569 June 2001 Pittsburgh Pennsylvania U S A...