![DSEGenset DSE8610 Operator'S Manual Download Page 99](http://html1.mh-extra.com/html/dsegenset/dse8610/dse8610_operators-manual_2535081099.webp)
Protections
99
8.8 SHORT CIRCUIT AND EARTH FAULT ALARM
When the module is suitably connected using the ‘Earth Fault CT’. The module measures Earth Fault
and can optionally be configured to generate an alarm condition (shutdown or electrical trip) when a
specified level is surpassed.
Short Circuit
alarm operates in the same way as the Earth Fault, using the same curve formula, but
typically uses a lower value for K (time multiplier) to give a faster acting trip.
If the A
larm
is enabled, the DSE8610 Series controller begins following the IDMT ‘curve’. If the current
surpasses the
Trip
for an excess of time, the Alarm triggers (
Shutdown
or
Electric trip
as selected in
Action
).
The higher the fault, the faster the trip. The speed of the trip is dependent upon the fixed formula:
T = K x 0.14 / ( ( I / I
s
)
0.02
-1 )
Where:
T is the tripping time in seconds (accurate to +/- 5% or +/- 50ms (whichever is the greater)
K is the time multiplier setting
I is the actual earth current measured
Is is the trip setting value
The settings shown in the example above are a screen capture of the DSE factory settings, taken from
the DSE Configuration Suite software.
I
S
(Trip setting
value)
K (time multiplier setting)
K (time multiplier setting)
I
S
(Trip setting
value)
Summary of Contents for DSE8610
Page 47: ...Installation 47 4 2 2 3 PHASE 4 WIRE WITHOUT EARTH FAULT PROTECTION...
Page 51: ...Installation 51 4 3 2 SINGLE PHASE WITHOUT EARTH FAULT...
Page 53: ...Installation 53 4 3 4 2 PHASE L1 L2 3 WIRE WITHOUT EARTH FAULT...
Page 55: ...Installation 55 4 3 6 2 PHASE L1 L3 3 WIRE WITHOUT EARTH FAULT MEASURING...
Page 118: ...Intentionally Left Blank 118...