Scheduler
105
10 SCHEDULER
DSE8600 Series contains an inbuilt exercise run scheduler, capable of automatically starting and
stopping the set. Up to 16 scheduled start/stop sequences can be configured to repeat on a 7-day or
28-day cycle.
Scheduled runs may be on load or off load depending upon module configuration.
Example
Screen capture from DSE
Configuration Suite Software
showing the configuration of the
Exercise Scheduler.
In this example the set will start at
09:00 on Monday and run for 5
hours, then start at 13:30 on
Tuesday and run for 30 minutes.
10.1 STOP MODE
•
Scheduled runs will not occur when the module is in STOP/RESET mode.
10.2 MANUAL MODE
•
Scheduled runs will not occur when the module is in MANUAL mode.
•
Activation of a Scheduled Run ‘On Load’ when the module is operating OFF LOAD in Manual
mode will have no effect, the set continues to run OFF LOAD
10.3 AUTO MODE
•
Scheduled runs will operate ONLY if the module is in AUTO mode with no Shutdown or
Electrical Trip alarm present.
•
If the module is in STOP or MANUAL mode when a scheduled run begins, the engine is not
started. However, if the module moves into AUTO mode during a scheduled run, the engine is
called to start.
•
Depending upon configuration by the system designer, an external input can be used to inhibit
a scheduled run.
•
If the engine is running OFF LOAD in AUTO mode and a scheduled run configured to ‘On
Load’ begins, the set is placed ON LOAD for the duration of the Schedule.
Summary of Contents for DSE8610
Page 47: ...Installation 47 4 2 2 3 PHASE 4 WIRE WITHOUT EARTH FAULT PROTECTION...
Page 51: ...Installation 51 4 3 2 SINGLE PHASE WITHOUT EARTH FAULT...
Page 53: ...Installation 53 4 3 4 2 PHASE L1 L2 3 WIRE WITHOUT EARTH FAULT...
Page 55: ...Installation 55 4 3 6 2 PHASE L1 L3 3 WIRE WITHOUT EARTH FAULT MEASURING...
Page 118: ...Intentionally Left Blank 118...