Operation
78
6.3 SMS CONTROL
NOTE: Only available in version DSE86xx version 5.1+ modules with a suitable GSM
modem connected to the RS232 port and configured to receive the control commands.
The
SMS Control
feature (if enabled) allows the user to send control commands to a DSE86xx via
SMS message. There are five control commands that the user can send to the module, these control
commands are in the table below.
NOTE: Multiple SMS Control Commands CANNOT be sent in a single SMS message.
Control Command
Number
Module Action
1
Start the generator off load if in the ‘Auto’ position.
2
Start the generator on load if in the ‘Auto’ position..
3
Cancel an SMS start request.
4
Put the module into the ‘STOP’ position.
5
Put the module into the ‘AUTO’ position.
To send an SMS command, the user will need (if configured) the
SMS Control Pin
Number
and
the
Control Command Number.
Only these numbers must be included in the SMS, the module will not
respond to any SMS with extra characters or missing PIN number (if configured). Below is an example
how to start and run the generator on load by SMS message.
NOTE: There must be a space between the
SMS PIN Number
and the
Control Command
Number
SMS Message 1
This SMS message will place the module into the AUTO position.
0123 5
SMS Message 2
This SMS message will start and run the generator on load..
0123 2
SMS Message3
This SMS message will remove the start and run command given by the
previous SMS message and leave the module in the AUTO position
0123 3
SMS Message 4
This SMS message will place the module into the STOP position.
0123 4
Example screen shot of
SMS Control
setup
in the DSE Configuration Suite
6.4 STOP MODE
Pin
Number
Control
Command
Number
Summary of Contents for DSE8610
Page 47: ...Installation 47 4 2 2 3 PHASE 4 WIRE WITHOUT EARTH FAULT PROTECTION...
Page 51: ...Installation 51 4 3 2 SINGLE PHASE WITHOUT EARTH FAULT...
Page 53: ...Installation 53 4 3 4 2 PHASE L1 L2 3 WIRE WITHOUT EARTH FAULT...
Page 55: ...Installation 55 4 3 6 2 PHASE L1 L3 3 WIRE WITHOUT EARTH FAULT MEASURING...
Page 118: ...Intentionally Left Blank 118...