Specifications
30
3.9 SOUNDER
DSE8600 Series features an internal sounder to draw attention to warning, shutdown and electrical trip
alarms.
Sounder level
64db @ 1m
3.9.1 ADDING AN EXTERNAL SOUNDER TO THE APPLICATION
Should an external alarm or indicator be required, this can be achieved by using the DSE
Configuration Suite PC software to configure an auxiliary output for “Audible Alarm”, and by
configuring an auxiliary input for “Alarm Mute” (if required).
The audible alarm output activates and de-activates at the same time as the module’s internal
sounder. The Alarm mute input and internal alarm mute button activate ‘in parallel’ with each other.
Either signal will mute both the internal sounder and audible alarm output.
Example of configuration to achieve external sounder with external alarm mute button:
3.10 ACCUMULATED INSTRUMENTATION
NOTE: When an accumulated instrumentation value exceeds the maximum number as
listed below, it will reset and begin counting from zero again.
Engine hours run
Maximum 99999 hrs 59 minutes (approximately 11yrs 4months)
Number of starts
1,000,000 (1 million)
The number of logged Engine Hours and Number of Starts can be set/reset using the DSE
Configuration Suite PC software. Depending upon module configuration, this may have been PIN
number locked by your generator supplier
Summary of Contents for DSE8610
Page 47: ...Installation 47 4 2 2 3 PHASE 4 WIRE WITHOUT EARTH FAULT PROTECTION...
Page 51: ...Installation 51 4 3 2 SINGLE PHASE WITHOUT EARTH FAULT...
Page 53: ...Installation 53 4 3 4 2 PHASE L1 L2 3 WIRE WITHOUT EARTH FAULT...
Page 55: ...Installation 55 4 3 6 2 PHASE L1 L3 3 WIRE WITHOUT EARTH FAULT MEASURING...
Page 118: ...Intentionally Left Blank 118...