6.6.5 MANUAL SPEED CONTROL
•
Navigate to the instruments page using the
buttons and locate ENGINE SPEED.
is
shown on the module display to indicate that this feature is available.
•
Press the
button to enter edit mode
•
Press
(up or down) to change the engine speed.
•
Press the
button again to exit the editor and leave the engine running at the newly
selected speed.
6.6.6 STOPPING SEQUENCE
In manual mode the set will continue to run until either :
•
The
stop button
is pressed – The set will immediately stop if
Coolddown in Stop Mode
is
disabled, or the set will go to
cooldown
if
Coolddown in Stop Mode
is enabled and will stop
until the
Cooling Time
timer expires.
•
The
auto button
is pressed. The set will observe all auto mode start requests and
stopping timers before beginning the
Auto mode stopping sequence
.