Protections
88
8 PROTECTIONS
When an alarm is present, the Audible Alarm will sound and the Common alarm LED if configured will
illuminate.
The audible alarm can be silenced by pressing the
Mute button
The LCD display will jump from the ‘Information page’ to display the Alarm Page
Alarm 1/2
Warning
Low oil pressure
The LCD will display multiple alarms E.g. “High Engine Temperature shutdown”, “Emergency Stop”
and “Low Coolant Warning”. These will automatically scroll in the order that they occurred.
In the event of a warning alarm, the LCD will display the appropriate text. If a shutdown then occurs,
the module will again display the appropriate text.
Example:-
Alarm 1/2
Warning
Oil pressure Low
Alarm 2/2
Shutdown
Coolant Temperature High
The type of alarm. E.g. Shutdown or warning
The nature of alarm, e.g. Low oil pressure
Number of present alarms. This is alarm 1 of a
total of 2 present alarms