![DSEGenset DSE8610 Operator'S Manual Download Page 34](http://html1.mh-extra.com/html/dsegenset/dse8610/dse8610_operators-manual_2535081034.webp)
Specifications
34
3.12 APPLICABLE STANDARDS
BS 4884-1
This document conforms to BS4884-1 1992 Specification for presentation
of essential information.
BS 4884-2
This document conforms to BS4884-2 1993 Guide to content
BS 4884-3
This document conforms to BS4884-3 1993 Guide to presentation
BS EN 60068-2-1
(Minimum temperature)
-30
°
C (-22
°
F)
BS EN 60068-2-2
(Maximum
temperature)
+70
°
C (158
°
F)
BS EN 60950
Safety of information technology equipment, including electrical business
equipment
BS EN 61000-6-2
EMC Generic Immunity Standard (Industrial)
BS EN 61000-6-4
EMC Generic Emission Standard (Industrial)
BS EN 60529
(Degrees of protection
provided by enclosures)
(see overleaf)
IP65 (front of module when installed into the control panel with the supplied
sealing gasket)
IP42 (front of module when installed into the control panel WITHOUT being
sealed to the panel)
UL508
NEMA rating
(Approximate)
(see overleaf)
12 (Front of module when installed into the control panel with the supplied
sealing gasket).
2 (Front of module when installed into the control panel WITHOUT being
sealed to the panel)
IEEE C37.2
(Standard Electrical
Power System Device
Function Numbers and
Contact Designations)
Under the scope of IEEE 37.2,
function numbers can also be used to
represent functions in microprocessor devices and software programs
.
The 8610 series controller is device number 11L-8610 (Multifunction device
protecting Line (generator) – 8610 series module).
As the module is configurable by the generator OEM, the functions covered
by the module will vary. Under the module’s factory configuration, the
device numbers included within the module are :
2 – Time delay starting or closing relay
6 – Starting circuit breaker
27AC – AC undervoltage relay
27DC – DC undervoltage relay
30 – annunciator relay
42 – Running circuit breaker
50 – instantaneous overcurrent relay
51 – ac time overcurrent relay
52 – ac circuit breaker
53DC – exciter or dc generator relay
54 – turning gear engaging device
59AC – AC overvoltage relay
59DC – DC overvoltage relay
62 – time delay stopping or opening relay
63 – pressure switch
74– alarm relay
81 – frequency relay
86 – lockout relay
In line with our policy of continual development, Deep Sea Electronics, reserve the right to change specification without notice.
Summary of Contents for DSE8610
Page 47: ...Installation 47 4 2 2 3 PHASE 4 WIRE WITHOUT EARTH FAULT PROTECTION...
Page 51: ...Installation 51 4 3 2 SINGLE PHASE WITHOUT EARTH FAULT...
Page 53: ...Installation 53 4 3 4 2 PHASE L1 L2 3 WIRE WITHOUT EARTH FAULT...
Page 55: ...Installation 55 4 3 6 2 PHASE L1 L3 3 WIRE WITHOUT EARTH FAULT MEASURING...
Page 118: ...Intentionally Left Blank 118...