Protections
98
With typical settings as above, the tripping curve is followed as shown below.
This allows for overload of the set to the limits of the
Typical Brushless Alternator
whereby 110%
overload is permitted for 1 hour.
If the set load reduces, the controller then
follows
a cooling curve. This means that a second overload
condition may trip much sooner than the first as the controller
knows
if the windings have not cooled
sufficiently.
For further details on the
Thermal damage curve
of your alternator, you are referred to your alternator
manufacturer and generator supplier.