Description Of Controls
74
5.6 CONTROLS
Stop / Reset
This button places the module into its
Stop/Reset
mode. This will clear any alarm
conditions for which the triggering criteria have been removed. If the engine is running
and the module is in Stop mode, the module will automatically instruct the changeover
device to unload the generator
(‘
Close Generator
’
becomes inactive (if used))
. The fuel
supply de-energises and the engine comes to a standstill. Should a
remote start signal
be present while operating in this mode, a remote start will not occur.
Manual
This mode allows manual control of the generator functions. Once in
Manual mode
the
module will respond to the start
button, start the engine, and run off load. If the
engine is running off-load in the
Manual mode
and a
remote start signal
becomes
present, the module will automatically instruct the changeover device to place the
generator on load
(‘
Close Generator
’
becomes active (if used))
. Upon removal of the
remote start signal
, the generator remains on load until either selection of the
‘STOP/RESET’
or
‘AUTO’
modes.
For further details, please see the more detailed description of ‘Manual operation’
elsewhere in this manual.
Auto
This button places the module into its
‘Automatic’
mode. This mode allows the module
to control the function of the generator automatically. The module will monitor the
remote start
input and mains supply status and once a start request is made, the set will
be automatically started and placed on load.
Upon removal of the starting signal, the module will automatically transfer the load from
the generator and shut the set down observing the
stop delay
timer and
cooling
timer as
necessary. The module will then await the next start event.
For further details, please
see the more detailed description of ‘Auto operation’ elsewhere in this manual.
Start
This button is only active in STOP/RESET
or MANUAL
mode.
Pressing this button in manual or test mode will
start the engine and run off load
(manual) or on load (test).
Pressing this button in STOP/RESET mode will turn on the CAN engine ECU (when
correctly configured and fitted to a compatible engine ECU)
Mute / Lamp Test
This button silences the audible alarm if it is sounding and illuminates all of the LEDs as
a lamp test feature/
When correctly configured and fitted to a compatible engine ECU, pressing this button in
STOP/RESET mode after pressing the START
button (to power the ECU) will
cancel any “passive” alarms on the engine ECU.
Transfer to generator
Allows the operator to transfer the load to the generator, synchronising first if required.
(when in Manual mode only)
Open generator (DSE8610 only)
Allows the operator to open the generator breaker (when in Manual mode only)
Menu navigation
Used for navigating the instrumentation, event log and configuration screens.
For further details, please see the more detailed description of these items elsewhere in
this manual.
Summary of Contents for DSE8610
Page 47: ...Installation 47 4 2 2 3 PHASE 4 WIRE WITHOUT EARTH FAULT PROTECTION...
Page 51: ...Installation 51 4 3 2 SINGLE PHASE WITHOUT EARTH FAULT...
Page 53: ...Installation 53 4 3 4 2 PHASE L1 L2 3 WIRE WITHOUT EARTH FAULT...
Page 55: ...Installation 55 4 3 6 2 PHASE L1 L3 3 WIRE WITHOUT EARTH FAULT MEASURING...
Page 118: ...Intentionally Left Blank 118...