![DSEGenset DSE8610 Operator'S Manual Download Page 16](http://html1.mh-extra.com/html/dsegenset/dse8610/dse8610_operators-manual_2535081016.webp)
Specifications
16
3.6 OUTPUTS
Ten (10) digital outputs are fitted to the DSE8610 controller. Additional outputs are provided for by
adding up to ten (10) external relay boards (DSE2157). This allows for up to 80 additional digital
outputs.
3.6.1 OUTPUTS A & B
Type
Normally used for Fuel / Start outputs. Fully configurable for other purposes if the module is
configured to control an electronic engine. Supplied from Emergency Stop terminal 3.
Rating
15A resistive @ 35V
3.6.2 OUTPUTS C & D
Type
Voltage free relays, fully configurable, normally used for generator / mains load switch
control.
Rating
8A resistive @ 250 V AC
3.6.2.1
CONTACTOR COILS
Use output D, the normally open relay:
3.6.2.2
UNDERVOLTAGE (UV COILS)
Use output C, the normally closed relay :
Generator
DSE output drives the contactor coil, via external slave relay if required.
When the DSE module requires the contactor closed, the output energises (closing the internal
relay)
When the DSE module requires the contactor to be open, the output is de-energised (opening
the internal relay)
Generator
DSE output drives the UV coil, via external slave relay if required.
When the generator starts, the UV is powered via the normally closed relay. The breaker is
now ready for the close signal to be given. When the breaker is to be opened, the Open
Generator Pulse relay is operated, removing power from the UV coil for one second. This
causes the breaker to trip (open) as the UV is no longer
powered. The Open Generator
Pulse relay switches back to its closed state, ready to power the UV coil the next time the
generator starts.
Summary of Contents for DSE8610
Page 47: ...Installation 47 4 2 2 3 PHASE 4 WIRE WITHOUT EARTH FAULT PROTECTION...
Page 51: ...Installation 51 4 3 2 SINGLE PHASE WITHOUT EARTH FAULT...
Page 53: ...Installation 53 4 3 4 2 PHASE L1 L2 3 WIRE WITHOUT EARTH FAULT...
Page 55: ...Installation 55 4 3 6 2 PHASE L1 L3 3 WIRE WITHOUT EARTH FAULT MEASURING...
Page 118: ...Intentionally Left Blank 118...