Specification
Page 15 of 188
057-254 ISSUE: 2
2.5 VOLTAGE & FREQUENCY SENSING
Description
Specification
Measurement Type
True RMS conversion
Sample Rate
40 kHz
Harmonics
Up to 21
st
or better
Input Impedance
300 k
Ω
phase to neutral
Phase To Neutral
15 V (minimum required for sensing frequency) to 415 V AC
(absolute maximum)
Suitable for 345 V AC nominal
(±20 % for under/overvoltage detection)
Phase To Phase
25 V (minimum required for sensing frequency) to 720 V AC
(absolute maximum)
Suitable for 600 V AC nominal
(±20 % for under/overvoltage detection)
Common Mode Offset From Earth
100 V AC (max)
Resolution
1 V AC phase to neutral
2 V AC phase to phase
Accuracy
±1 % of full scale phase to neutral
±2 % of full scale phase to phase
Minimum Frequency
3.5 Hz
Maximum Frequency
75.0 Hz
Frequency Resolution
0.1 Hz
Frequency Accuracy
±0.05 Hz
2.6 CURRENT SENSING
Description
Specification
Measurement Type
True RMS conversion
Sample Rate
40 kHz
Harmonics
Up to 21
st
or better
Nominal CT Secondary Rating
1 A and 5 A
Maximum Continuous Current
5 A
Overload Measurement
15 A
Absolute Maximum Overload
50 A for 1 second
Burden
0.5 VA (0.02
Ω
current shunts)
Common Mode Offset
70 V peak plant ground to CT common terminal under fault
condition
Resolution
25 mA
Accuracy
±1 % of Nominal (excluding CT error)
Summary of Contents for 8610 MKII
Page 63: ...Installation Page 63 of 188 057 254 ISSUE 2 3 4 2 SINGLE PHASE L1 N 2 WIRE WITHOUT EARTH FAULT...
Page 69: ...Installation Page 69 of 188 057 254 ISSUE 2 3 4 8 2 PHASE L1 L2 3 WIRE WITHOUT EARTH FAULT...
Page 71: ...Installation Page 71 of 188 057 254 ISSUE 2 3 4 10 2 PHASE L1 L3 3 WIRE WITHOUT EARTH FAULT...
Page 72: ...Installation 057 254 ISSUE 2 Page 72 of 188 3 4 11 3 PHASE 3 WIRE DETLA WITHOUT EARTH FAULT...
Page 187: ...This Page is Intentionally Blank...
Page 188: ...This Page is Intentionally Blank...