Installation
057-254 ISSUE: 2
Page 54 of 188
3.2.8 RS485
NOTE: For further details of module configuration, refer to DSE Publication: 057-238
DSE8610 MKII Configuration Suite PC Software Manual.
NOTE: A 120
Ω
termination resistor must be fitted across terminals A and B if the DSE
module is the first or last device on the R485 link.
NOTE: Screened 120
Ω
Ω
Ω
Ω
impedance cable specified for use with RS485 must be used for
the RS485 link.
DSE stock and supply Belden cable 9841 which is a high quality 120
Ω
Ω
Ω
Ω
impedance cable
suitable for CAN use (DSE part number 016-030)
Pin
No
Description
Cable
Size
Notes
RS485
1
71
RS485 Port Screen
Shield
Use only 120
Ω
CAN or RS485 approved cable
72
RS485 Port B (+)
0.5 mm²
AWG 20
Connect to RXD+ and TXD+
Use only 120
Ω
CAN or RS485 approved cable
73
RS485 Port A (-)
0.5 mm²
AWG 20
Connect to RXD- and TXD-
Use only 120
Ω
CAN or RS485 approved cable
RS485
2
74
RS485 Port Screen
Shield
Use only 120
Ω
CAN or RS485 approved cable
75
RS485 Port B (+)
0.5 mm²
AWG 20
Connect to RXD+ and TXD+
Use only 120
Ω
CAN or RS485 approved cable
76
RS485 Port A (-)
0.5 mm²
AWG 20
Connect to RXD- and TXD-
Use only 120
Ω
CAN or RS485 approved cable
Summary of Contents for 8610 MKII
Page 63: ...Installation Page 63 of 188 057 254 ISSUE 2 3 4 2 SINGLE PHASE L1 N 2 WIRE WITHOUT EARTH FAULT...
Page 69: ...Installation Page 69 of 188 057 254 ISSUE 2 3 4 8 2 PHASE L1 L2 3 WIRE WITHOUT EARTH FAULT...
Page 71: ...Installation Page 71 of 188 057 254 ISSUE 2 3 4 10 2 PHASE L1 L3 3 WIRE WITHOUT EARTH FAULT...
Page 72: ...Installation 057 254 ISSUE 2 Page 72 of 188 3 4 11 3 PHASE 3 WIRE DETLA WITHOUT EARTH FAULT...
Page 187: ...This Page is Intentionally Blank...
Page 188: ...This Page is Intentionally Blank...