Specification
057-254 ISSUE: 2
Page 22 of 188
2.8 OUTPUTS
2.8.1 DC OUTPUTS A & B (FUEL & START)
Description
Specification
Type
Normally used as Fuel & Start outputs.
Fully configurable for other purposes if the module is configured to control an
electronic engine.
Rating
15 A resistive at Emergency Stop supply.
2.8.2 CONFIGURABLE VOLT-FREE RELAY OUTPUTS C & D
Description
Specification
Type
Normally used for load switching control
Fully configurable volt-free relays.
Output C normally closed and Output D normal open.
Rating
8 A resistive at 250 V AC
2.8.3 CONFIGURABLE DC OUTPUTS E, F, G, H, I, J, K & L
Description
Specification
Type
Fully configurable, supplied from DC supply terminal 2.
Rating
2 A resistive at module supply.
2.8.4 GOVERNOR CONTROL OUTPUT
Description
Specification
Arrangement
Supplied from DC supply terminal 2
Type
Isolated DC output, voltage controlled
Voltage Range
-5 V to +10 V DC
Max Common Mode Voltage
±1 kV
Resolution
Less than 1 mV
Accuracy
±1%
Minimum Load
500
Ω
2.8.5 AVR CONTROL OUTPUT
Description
Specification
Arrangement
Supplied from DC supply terminal 2
Type
Isolated DC output, voltage controlled
Voltage Range
-5 V to +10 V DC
Max Common Mode Voltage
±3 kV
Resolution
Less than 1 mV
Accuracy
±1 %
Minimum Load
500
Ω
Summary of Contents for 8610 MKII
Page 63: ...Installation Page 63 of 188 057 254 ISSUE 2 3 4 2 SINGLE PHASE L1 N 2 WIRE WITHOUT EARTH FAULT...
Page 69: ...Installation Page 69 of 188 057 254 ISSUE 2 3 4 8 2 PHASE L1 L2 3 WIRE WITHOUT EARTH FAULT...
Page 71: ...Installation Page 71 of 188 057 254 ISSUE 2 3 4 10 2 PHASE L1 L3 3 WIRE WITHOUT EARTH FAULT...
Page 72: ...Installation 057 254 ISSUE 2 Page 72 of 188 3 4 11 3 PHASE 3 WIRE DETLA WITHOUT EARTH FAULT...
Page 187: ...This Page is Intentionally Blank...
Page 188: ...This Page is Intentionally Blank...