Specification
057-254 ISSUE: 2
Page 14 of 188
2.3 TERMINAL SPECIFICATION
Description
Specification
Connection Type
Two part connector.
Male part fitted to module
Female part supplied in module
packing case - Screw terminal,
rising clamp, no internal spring.
Example showing cable entry and screw
terminals of a 10 way connector
Minimum Cable Size
0.5 mm² (AWG 24)
Maximum Cable Size
2.5 mm² (AWG 12)
Tightening Torque
0.5 Nm (4.5 lb-in)
Wire Strip Length
7 mm (9/32”)
2.4 POWER SUPPLY REQUIREMENTS
Description
Specification
Minimum Supply Voltage
5 V continuous
Cranking Dropouts
Able to survive 0 V for 100 ms providing the supply was at least
was greater than 5 V for 2 seconds before the dropout and
recovers to 5 V afterwards.
Maximum Supply Voltage
35 V continuous (60 V protection)
Reverse Polarity Protection
-35 V continuous
Maximum Operating Current
530 mA at 12 V
280 mA at 24 V
Maximum Standby Current
320 mA at 12 V
120 mA at 24 V
Maximum Current When In Sleep
Mode
140 mA at 12 V
75 mA at 24 V
Typical Power
(Controller On, Heater Off)
3.8 W to 4.1 W
Typical Power
(Controller On, Heater On)
6.8 W to 7.1 W
2.4.1 MODULE SUPPLY INSTRUMENTATION DISPLAY
Description
Specification
Range
0 V to 70 V DC (Maximum continuous operating voltage of 35 V DC)
Resolution
0.1 V
Accuracy
1 % full scale (±0.35 V)
Summary of Contents for 8610 MKII
Page 63: ...Installation Page 63 of 188 057 254 ISSUE 2 3 4 2 SINGLE PHASE L1 N 2 WIRE WITHOUT EARTH FAULT...
Page 69: ...Installation Page 69 of 188 057 254 ISSUE 2 3 4 8 2 PHASE L1 L2 3 WIRE WITHOUT EARTH FAULT...
Page 71: ...Installation Page 71 of 188 057 254 ISSUE 2 3 4 10 2 PHASE L1 L3 3 WIRE WITHOUT EARTH FAULT...
Page 72: ...Installation 057 254 ISSUE 2 Page 72 of 188 3 4 11 3 PHASE 3 WIRE DETLA WITHOUT EARTH FAULT...
Page 187: ...This Page is Intentionally Blank...
Page 188: ...This Page is Intentionally Blank...