Description of Controls
Page 103 of 188
057-254 ISSUE: 2
Connected to an RS232 GSM Modem
When the module is powered up, it sends ‘initialisation strings’ to the connected modem. It is
important therefore that the modem is already powered, or is powered up at the same time as the
module. At regular intervals after power up, the modem is reset, and reinitialised, to ensure the
modem does not ‘hang up’.
If the module does not correctly communicate with the modem, “Modem initialising’ appears on the
Serial Port instrument screen as shown overleaf.
If the module is set for “incoming calls” or for “incoming and outgoing calls”, once the modem is
dialled, it answers after two rings (using the factory setting ‘initialisation strings). Once the call is
established, all data is passed between the dialling PC and the module.
If the module is set for “outgoing calls” or for “incoming and outgoing calls”, then the module dials out
whenever an alarm is generated.
NOTE: Not all alarms generate a dial out command; this is dependant upon module
configuration of the event log. Any event configured to be recorded in the event log causes the
modem to dial out to a PC.
Many GSM modems are fitted with a status LED to show operator cell status and ringing indicator.
These are a useful troubleshooting tool.
In the case of GSM connection problems, try calling the DATA number of the SIMCARD with an
ordinary telephone. There should be two rings, followed by the modem answering the call and then
‘squealing’. If this does not happen, check all modem connections and double check with the SIM
provider that it is a DATA SIM and can operate as a data modem. DATA is NOT the same as FAX or
GPRS and is often called Circuit Switched Data (CSD) by the SIM provider.
Press the Scroll Down
button view the modem GSM
status....
NOTE: In the case of GSM modems, it is important that a DATA ENABLED SIM is used.
This is often a different number than the ‘voice number’ and is often called Circuit Switched
Data (CSD) by the SIM provider.
If the GSM modem is not purchased from DSE, ensure that it has been correctly set to operate at
9600 baud.
Currently connected GSM
operator and signal strength.
Summary of Contents for 8610 MKII
Page 63: ...Installation Page 63 of 188 057 254 ISSUE 2 3 4 2 SINGLE PHASE L1 N 2 WIRE WITHOUT EARTH FAULT...
Page 69: ...Installation Page 69 of 188 057 254 ISSUE 2 3 4 8 2 PHASE L1 L2 3 WIRE WITHOUT EARTH FAULT...
Page 71: ...Installation Page 71 of 188 057 254 ISSUE 2 3 4 10 2 PHASE L1 L3 3 WIRE WITHOUT EARTH FAULT...
Page 72: ...Installation 057 254 ISSUE 2 Page 72 of 188 3 4 11 3 PHASE 3 WIRE DETLA WITHOUT EARTH FAULT...
Page 187: ...This Page is Intentionally Blank...
Page 188: ...This Page is Intentionally Blank...