Operation
Page 113 of 188
057-254 ISSUE: 2
5.2 STOP/RESET MODE
NOTE: If a digital input configured to Panel Lock is active, changing module modes is not
possible. Viewing the instruments and event logs is NOT affected by Panel Lock.
NOTE: For further details of module configuration, refer to DSE Publication: 057-238
DSE8610 MKII Configuration Suite PC Software Manual.
Stop/Reset Mode is activated by pressing the Stop/Reset Mode
button.
The LED above the Stop/Reset Mode
button illuminates to indicate Stop/Reset Mode
operation.
In Stop/Reset Mode
, the module removes the generator from load (if necessary) before stopping
the generator.
If the generator does not stop when requested, the Fail To Stop alarm is activated (subject to the
setting of the Fail to Stop timer). To detect the engine at rest the following must occur:
•
Engine speed is zero as detected by the CAN ECU
•
Generator AC Voltage and Frequency must be zero.
•
Engine Charge Alternator Voltage must be zero.
•
Oil pressure sensor must indicate low oil pressure
When the engine has stopped and the module is in the Stop/Reset Mode
, it is possible to send
configuration files to the module from DSE Configuration Suite PC software and to enter the Front
Panel Editor to change parameters.
Any latched alarms that have been cleared are reset when Stop/Reset Mode
is entered.
The engine is not started when in Stop/Reset Mode
. If start signals are given, the input is
ignored until Auto Mode
is entered.
When left in Stop/Reset Mode
with no presses of the fascia buttons, no form of communication
active and configured for Power Save Mode, the module enters Power Save Mode. To ‘wake’ the
module, press any fascia control buttons.
5.2.1 ECU OVERRIDE
Pressing the Start
button in Stop/Reset Mode
powers up the engine’s ECU but does not
start the engine. This can be used to check the status of the CAN communication and to prime the
fuel system.
Power Save Mode in the
DSE Configuration Suite
Software
Summary of Contents for 8610 MKII
Page 63: ...Installation Page 63 of 188 057 254 ISSUE 2 3 4 2 SINGLE PHASE L1 N 2 WIRE WITHOUT EARTH FAULT...
Page 69: ...Installation Page 69 of 188 057 254 ISSUE 2 3 4 8 2 PHASE L1 L2 3 WIRE WITHOUT EARTH FAULT...
Page 71: ...Installation Page 71 of 188 057 254 ISSUE 2 3 4 10 2 PHASE L1 L3 3 WIRE WITHOUT EARTH FAULT...
Page 72: ...Installation 057 254 ISSUE 2 Page 72 of 188 3 4 11 3 PHASE 3 WIRE DETLA WITHOUT EARTH FAULT...
Page 187: ...This Page is Intentionally Blank...
Page 188: ...This Page is Intentionally Blank...