Protections
Page 143 of 188
057-254 ISSUE: 2
6.5 SHUTDOWN ALARMS
NOTE: The fault condition must be resolved before the alarm can be reset. If the fault
condition remains, it is not possible to reset the alarm (the exception to this is the Oil Pressure
Low alarm and similar Active From Safety On alarms, as the oil pressure is low with the engine
at rest).
Shutdown Alarms are latching and immediately stop the Generator. On initiation of the shutdown
condition the module de-activates the Close Gen Output outputs to remove the load from the
generator. Once this has occurred, the module shuts the generator set down immediately to prevent
further damage. To restart the generator the fault must be cleared and the alarm reset.
Example:
1/2 Alarm
Oil Pressure Low
Shutdown
In the event of an alarm the LCD jumps to the alarms page and scrolls through all active alarms.
Shutdown Alarms are latching alarms and to remove the fault, press the Stop/Reset Mode
button
on the module.
Fault
Description
2130 ID 1 to 4 Analogue Input
E to H High
NOTE: Due to module configuration the alarm message
that appears on the display may be different. For further details
of module configuration, refer to DSE Publication: 057-238
DSE8610 MKII Configuration Suite PC Software Manual.
The module detected that an analogue input value of a DSE2130
had risen above the Flexible Sensor High Alarm Trip level.
2130 ID 1 to 4 Analogue Input
E to H Low
NOTE: Due to module configuration the alarm message
that appears on the display may be different. For further details
of module configuration, refer to DSE Publication: 057-238
DSE8610 MKII Configuration Suite PC Software Manual.
The module detected that an analogue input value of a DSE2130
had fallen below the Flexible Sensor Low Alarm Trip level.
Continued over page…
Summary of Contents for 8610 MKII
Page 63: ...Installation Page 63 of 188 057 254 ISSUE 2 3 4 2 SINGLE PHASE L1 N 2 WIRE WITHOUT EARTH FAULT...
Page 69: ...Installation Page 69 of 188 057 254 ISSUE 2 3 4 8 2 PHASE L1 L2 3 WIRE WITHOUT EARTH FAULT...
Page 71: ...Installation Page 71 of 188 057 254 ISSUE 2 3 4 10 2 PHASE L1 L3 3 WIRE WITHOUT EARTH FAULT...
Page 72: ...Installation 057 254 ISSUE 2 Page 72 of 188 3 4 11 3 PHASE 3 WIRE DETLA WITHOUT EARTH FAULT...
Page 187: ...This Page is Intentionally Blank...
Page 188: ...This Page is Intentionally Blank...