Operation
057-254 ISSUE: 2
Page 114 of 188
5.3 MANUAL MODE
NOTE: If a digital input configured to Panel Lock is active, changing module modes is not
possible. Viewing the instruments and event logs is NOT affected by panel lock.
Manual Mode is activated by pressing the Manual Mode
button.
The LED above the Manual Mode
button illuminates to indicate Manual Mode
operations.
In Manual Mode
the generator does not start automatically
To begin the starting sequence, press the Start
button.
5.3.1 STARTING SEQUENCE
NOTE: There is no Start Delay in this mode of operation.
NOTE: If the unit has been configured for CAN, compatible ECU’s receives the start
command via CAN.
NOTE: For further details of module configuration, refer to DSE Publication: 057-238
DSE8610 MKII Configuration Suite PC Software Manual.
The fuel relay is energised and the engine is cranked.
If the engine fails to fire during this cranking attempt then the starter motor is disengaged for the
Crank Rest Timer duration after which the next start attempt is made. Should this sequence continue
beyond the set Number Of Attempts, the start sequence is terminated and the display shows Fail to
Start.
The starter motor is disengaged when the engine fires. Speed detection is factory configured to be
derived from the AC alternator output frequency, but can additionally be measured from a Magnetic
Pickup mounted on the flywheel or from the CANbus link to the engine ECU depending on module
configuration.
Additionally, rising oil pressure can be used to disconnect the starter motor (but cannot detect
underspeed or overspeed).
After the starter motor has disengaged, the Safety On Delay timer activates, allowing Oil Pressure,
High Engine Temperature, Under-speed, Charge Fail and any delayed Auxiliary fault inputs to
stabilise without triggering the fault.
Summary of Contents for 8610 MKII
Page 63: ...Installation Page 63 of 188 057 254 ISSUE 2 3 4 2 SINGLE PHASE L1 N 2 WIRE WITHOUT EARTH FAULT...
Page 69: ...Installation Page 69 of 188 057 254 ISSUE 2 3 4 8 2 PHASE L1 L2 3 WIRE WITHOUT EARTH FAULT...
Page 71: ...Installation Page 71 of 188 057 254 ISSUE 2 3 4 10 2 PHASE L1 L3 3 WIRE WITHOUT EARTH FAULT...
Page 72: ...Installation 057 254 ISSUE 2 Page 72 of 188 3 4 11 3 PHASE 3 WIRE DETLA WITHOUT EARTH FAULT...
Page 187: ...This Page is Intentionally Blank...
Page 188: ...This Page is Intentionally Blank...