Installation
057-254 ISSUE: 2
Page 50 of 188
3.2.3 MPU, ECU, MSC & DSENET
®
NOTE: For further details of module configuration, refer to DSE Publication: 057-238
DSE8610 MKII Configuration Suite PC Software Manual.
NOTE: For further details on connection to electronic engines, refer to DSE Publication:
057-004 Electronic Engines And DSE Wiring
NOTE: Screened 120
Ω
Ω
Ω
Ω
impedance cable specified for use with CAN must be used for the
CAN & MSC links.
DSE stock and supply Belden cable 9841 which is a high quality 120
Ω
Ω
Ω
Ω
impedance cable
suitable for CAN use (DSE part number 016-030)
NOTE: As a termination resistor is internally fitted to the controller, the controller must be
the ‘first’ unit on the DSENet
®
link. A termination resistor MUST be fitted to the ‘last’ unit on
the DSENet
®
link. For connection details, refer to section entitled Typical Wiring Diagram
elsewhere in this document.
Pin
No
Description
Cable
Size
Notes
23
Magnetic Pickup Positive
0.5 mm²
AWG 20
Connect To Magnetic Pickup Device
24
Magnetic Pickup Negative
0.5 mm²
AWG 20
Connect To Magnetic Pickup Device
25
Magnetic Pickup Screen
Shield
Connect To Ground At One End Only
ECU
26
ECU Port H
0.5 mm²
AWG 20
Use only 120
Ω
CAN or RS485 approved cable
27
ECU Port L
0.5 mm²
AWG 20
Use only 120
Ω
CAN or RS485 approved cable
28
ECU Port Screen
Shield
Use only 120
Ω
CAN or RS485 approved cable
29
DSENet
®
Expansion B
0.5 mm²
AWG 20
Use only 120
Ω
CAN or RS485 approved cable
30
DSENet
®
Expansion A
0.5 mm²
AWG 20
Use only 120
Ω
CAN or RS485 approved cable
31
DSENet
®
Expansion Screen
Shield
Use only 120
Ω
CAN or RS485 approved cable
MSC
32
MSC Port H
0.5 mm²
AWG 20
Use only 120
Ω
CAN or RS485 approved cable
33
MSC Port L
0.5 mm²
AWG 20
Use only 120
Ω
CAN or RS485 approved cable
34
MSC Port Screen
Shield
Use only 120
Ω
CAN or RS485 approved cable
GOV
35
Analogue Governor Output B
0.5mm²
AWG 20
Analogue Governor DC Output
36
Analogue Governor Output A
0.5mm²
AWG 20
Analogue Governor Output Reference
DO NOT CONNECT
DO NOT CONNECT
AVR
38
Analogue AVR Output B
0.5mm²
AWG 20
Analogue AVR DC Output
39
Analogue AVR Output A
0.5mm²
AWG 20
Analogue AVR Output Reference
Summary of Contents for 8610 MKII
Page 63: ...Installation Page 63 of 188 057 254 ISSUE 2 3 4 2 SINGLE PHASE L1 N 2 WIRE WITHOUT EARTH FAULT...
Page 69: ...Installation Page 69 of 188 057 254 ISSUE 2 3 4 8 2 PHASE L1 L2 3 WIRE WITHOUT EARTH FAULT...
Page 71: ...Installation Page 71 of 188 057 254 ISSUE 2 3 4 10 2 PHASE L1 L3 3 WIRE WITHOUT EARTH FAULT...
Page 72: ...Installation 057 254 ISSUE 2 Page 72 of 188 3 4 11 3 PHASE 3 WIRE DETLA WITHOUT EARTH FAULT...
Page 187: ...This Page is Intentionally Blank...
Page 188: ...This Page is Intentionally Blank...