Operation
057-254 ISSUE: 2
Page 120 of 188
5.6 MSC COMPATIBILITY MODE
NOTE: These settings enable the interface between the DSE86xx MKII controllers and the
legacy DSE55xx and DSE75xx controllers.
Parameter
Description
MSC Compatibility
NOTE: The DSE5560 and DSE7560 are not compatible
with the DSE8660 MKII, only one type of DSExx60 can be
connected on the MSC at any time (DSE5560/DSE7560 OR
DSE8660 MKII).
= The DSE86xx MKII is not be able to communicate with the
DSE55xx and DSE75xx series modules on the MSC Link.
= Communication between DSE86xx MKII and
DSE55xx/DSE75xx is enabled. The maximum number of
DSExx10 controllers is reduced to 16 and the maximum number
of DSExx60 controllers is reduced to 8.
P123 Ramp Enabled
NOTE: The P123 is only available for DSExx10 MKII
modules.
= The DSE8610 MKII uses MSC link for connection to other
DSE modules for ramping and load sharing.
= The DSE8610 MKII is connected to a DSE123 using the
MSC link to convert the MSC link to interface with Analogue
Load Share lines
P123 Frequency Trip
(Only Available when P123 Ramp option is enabled)
If the frequency changes by this amount when ramping down,
the module opens the generator breaker.
MSC Link compatibility with
DSE55xx/DSE75xx modules
Summary of Contents for 8610 MKII
Page 63: ...Installation Page 63 of 188 057 254 ISSUE 2 3 4 2 SINGLE PHASE L1 N 2 WIRE WITHOUT EARTH FAULT...
Page 69: ...Installation Page 69 of 188 057 254 ISSUE 2 3 4 8 2 PHASE L1 L2 3 WIRE WITHOUT EARTH FAULT...
Page 71: ...Installation Page 71 of 188 057 254 ISSUE 2 3 4 10 2 PHASE L1 L3 3 WIRE WITHOUT EARTH FAULT...
Page 72: ...Installation 057 254 ISSUE 2 Page 72 of 188 3 4 11 3 PHASE 3 WIRE DETLA WITHOUT EARTH FAULT...
Page 187: ...This Page is Intentionally Blank...
Page 188: ...This Page is Intentionally Blank...