Installation
Page 61 of 188
057-254 ISSUE: 2
3.3.4 TYPICAL ARRANGEMENT OF MSC LINK
NOTE: For further details of module configuration, refer to DSE Publication: 057-238
DSE8610 MKII Configuration Suite PC Software Manual.
NOTE: Screened 120
Ω
Ω
Ω
Ω
impedance cable specified for use with CAN must be used for the
DSENet
®
(RS485) connection.
DSE stock and supply Belden cable 9841 which is a high quality 120
Ω
Ω
Ω
Ω
impedance cable
suitable for DSENet
®
use (DSE part number 016-030)
NOTE: A termination resistor MUST be fitted to the first and last unit on the MSC link.
NOTE: If any number of DSE8x60 are on the MSC link, a maximum of 2x DSE8x80 can be
used. For each DSE8x80 used, the number of available DSE8x60s to be used reduces.
Total of 40 DSE modules can be connected to the MSC link made up of DSE8x10 (up to 32),
DSE8x60 (up to 16) and DSE8x80 (up to 16)
This gives the possibility of:
•
32 generators (DSE8x10) and 8 synchronising transfers (DSE8x60)
•
32 generators (DSE8x10) and 8 generator bus couplers (DSE8x80)
•
24 generators (DSE8x10) and 16 synchronising transfers (DSE8x60)
•
24 generators (DSE8x10) and 16 generator bus couplers (DSE8x80)
•
32 generators (DSE8x10), 14 synchronising transfers (DSE8x60) and
2 generator bus couplers (DSE8x80)
Summary of Contents for 8610 MKII
Page 63: ...Installation Page 63 of 188 057 254 ISSUE 2 3 4 2 SINGLE PHASE L1 N 2 WIRE WITHOUT EARTH FAULT...
Page 69: ...Installation Page 69 of 188 057 254 ISSUE 2 3 4 8 2 PHASE L1 L2 3 WIRE WITHOUT EARTH FAULT...
Page 71: ...Installation Page 71 of 188 057 254 ISSUE 2 3 4 10 2 PHASE L1 L3 3 WIRE WITHOUT EARTH FAULT...
Page 72: ...Installation 057 254 ISSUE 2 Page 72 of 188 3 4 11 3 PHASE 3 WIRE DETLA WITHOUT EARTH FAULT...
Page 187: ...This Page is Intentionally Blank...
Page 188: ...This Page is Intentionally Blank...