7. PRINCIPAL DATA
7-1 Readings on gauges
Marking
Reading
Unit
Engine speed
1500 / 1800
min
-1
Hour meter
Adding up
H
Engine temperature
below 95
°C
Engine oil pressure
Between 2.0 and 6.0
1)
x100kPa
Battery charging voltage
more than 26.0
V
Frequency
50 / 60
Hz
Load current
Below max. rating
A
Voltage
indicates
Phase-to-phase
voltage
V
1)
If the engine is cold, the pressure may be higher during starting.
7-2 Setting of switches
Switch
Function
Breaks at
Unit
Engine oil pressure
Alarm
3.0
×100kPa
Shut-down
2.0
×100kPa
Engine coolant temperature
Alarm
108
°C
Shut-down
108
°C
Engine coolant level
Shut-down
Coolant level
is low
Engine Overspeed
Shut-down
2140
min
-1
7-3 Reference conditions
Absolute inlet pressure………………………………………………………... 100kPa
Relative air humidity…………………………………………………………... 60%
Air inlet temperature…………………………………………………………....27°C
Generator load……………………………………………………………….....continuous
7-4 Limitations
Maximum ambient temperature……………………………………….......... 46°C
Maximum altitude……………………………………………………………… 1000m Maximum relative
air humidity………………………………………….................................…...85%