![Denyo DCA-600P Instruction Manual Download Page 20](http://html1.mh-extra.com/html/denyo/dca-600p/dca-600p_instruction-manual_2485066020.webp)
- 18 -
Settings for the Monitoring System
Parameter
State
Trip Point
Delay Time
Low Engine Oil Pressure
Warn Operator
On
300 kPa
(43.5 psi)
60 seconds
Action Alert
Always On
250 kPa
(36.3 psi)
2 seconds
Engine Shutdown
Always On
200 kPa
(29.0 psi)
2 seconds
High Engine Coolant Temperature
Warn Operator
On
104
°C (219°F)
60
seconds
Action Alert
Always On
105
°C(221°F)
10
seconds
Engine Shutdown
Always On
108
°C(226°F)
10
seconds
Engine Overspeed
Warn Operator
On
2000 RPM
1 second
Action Alert
Always On
2050 RPM
0 second
Engine Shutdown
Always On
2140 RPM
0 second
High Intake Manifold Air Temperature
Warn Operator
On
75
°C (167°F)
60
seconds
Action Alert
Always On
78°C (172°F)
10
seconds
High Fuel Supply Temperature
Warn Operator
On
60°C (140°F)
60
seconds
Action Alert
Always On
68°C (154°F)
60
seconds
High Boost Pressure
Warn Operator
On
300 kPa
(43.5 psi)
60 seconds
Action Alert
Always On
Map
5 seconds
Summary of Contents for DCA-600P