- 22 -
3. If it is impossible to run the engine regularly, extra precautions must be taken.
1) Consult the instruction manual for the engine.
2) Remove the battery. Store it in the same environment as for the machine. Keep the
battery clean and coat its terminals lightly with petroleum jelly. Recharge the battery
regularly.
3) If the electrolyte has dropped to the specified level, refill it.
4) Clean the generator. Oil or fuel spillage is not allowed. Protect all electrical components
against penetration by moisture.
5) Enclose the generator, except the bottom, with a plastic bag.
2-3-2 Preparing
for
operation
Before operating again the generator kept unused for a long time, remove the plastic bag,
VCI paper from the openings and silica gel from inside and check the generator thoroughly.
Further maintain the following items.
1. Consult the instruction manual for the engine.
2. Measure the insulation resistance of the generator with a 500-V insulation resistance tester.
The resistance must exceed 1 M
Ω
.
In case of measuringwith an insulation resistance tester over 500VDC current, disconnect
all connectors from the AVR located in the control box before measuring.
3. Replace the fuel filter cartridge and fill the fuel tank.
Vent the fuel system.
4. Reinstall and connect the battery. If necessary, recharge it.
5. Check the fan belt condition and tension; adjust if required.
6. Check and, if required, refill cooling water and oil.
7. Submit the generator to a test run.