- 33 -
3-2-4 Connecting the load
1. Check whether frequency, voltage and current conform with the ratings of the generator.
2. Install for the load cable, without excessive length, and lay it out in a safe way without forming
coils.
1. Cable clamp
2. Cable outlet
3. Ground terminal(for bonnet)
4. Output terminal U
5. Output terminal V
6. Output terminal W
7. Output terminal O
Fig. 8
3. When connecting output terminals (See Fig. 8.)
• Remove the protection cover of output terminals.
• Loosen the cable clamp and push the wire ends of the load cable through the clamp and cable
outlet.
• Connect the wires to the proper terminals: U/V/W, and if
required O, for 3-phase load
O/U, O/V and O/W for single-phase load
• Tighten the bolts securely.
• Reinstall the protecting cover in front of the output terminal board.
• Tighten the clamp to fasten the cable.