2-4 Installation
2-4-1 Installation
1. Install the generator on a well ventilated, horizontal, even and solid floor. If the floor is not horizontal
enough to keep the machine leveled, consult your sales distributor. When installing the machine on a
trailer, fasten the trailer and fix the wheels by stoppers. Avoid a site exposed to rain or high temperature.
The operating ambient conditions are atmospheric temperature of
-5 to 46°C, humidity of 85% or lower and altitude of 1000m or ower.
If the machine do not conform with the above conditions, consult your sales distributor.
2. Avoid a dusty site. If it is inevitable, provide protective devices.
3. Do not operate the machine in an atmosphere containing toxic or combustible gas. Otherwise
fire or explosion might occur in the machine. (Example: Near volatilizing paint solvent.)
4. Leave space for operation, inspection and maintenance; at least 1200 mm each on machine
front and rear and sides. See Fig. 6
Fig. 6
[ NOTE ]
: If the machine is operated in a smaller space than that shown above, the room
temperature will rise. Please reduce the generator output in such condition. Therefore
proper power reduction is necessary.
If the space required above the machine is not uniform, make a decision so that:
• The radiator can be refilled with cooling water.
• The exhaust pipe can be introduced.
• The exhaust can smoothly be discharged.