3-5 Starting
1. Insert the key in the operation switch. Turn the key to RUN keep on pushing start button to
start engine.
• Do not engage the starter for more than 10 seconds at a time; if the engine does not fire, wait
2 minutes before restarting.
• Consult your sales distributor if starting is in extremely cold conditions.
• If the engine would not start after several tries, check whether the fuel level is too low, air is
not bled sufficiently or the battery is discharged.
2. Make sure that the engine warning lamps is extinguished. If alight, stop the engine, check the
item for which it is alight and eliminate the cause.
• Check the engine indicator for normal readings.
3. Check whether the frequency meter read as shown below or not.
Frequency
Isochronous
Droop
50Hz operation
50.0Hz
51.3~51.8Hz
60Hz operation
60.0Hz
61.5~62.1Hz
• Check the voltmeter indication and, when the voltage is deviated from the rated voltage,
please contact your nearest Distributor.
4. Check the voltmeter indication and, if required, adjust with the voltage regulator knob.
Turning clockwise increases the voltage and vice versa.
5. When three-phase voltage is supplied, switch the three-phase circuit breaker to ON.
6. Switch on the load and check the frequency meter and voltmeter once more.
Adjust voltage if necessary.
Frequency (3-phase) Voltage
50Hz operation
50 Hz
190~220V or 380~440V
60Hz operation 60 Hz 190~240V or 380~480V