AH500 Hardware Manual
The functional specifications
Analog-to-digital
conversion
Voltage input
Rated input
range
-10 V~10 V
0 V~10 V
±5 V
0 V~5 V
1 V~5 V
Hardware
input range
-10.1 V~10.1 V -0.1 V~10.1 V -5.05 V~5.05 V -0.05 V~5.05 V 0.95 V~5.05 V
Hardware
resolution
16 bits
Input
impedance
>200 k
Ω
Absolute
input range
±15 V
Analog-to-digital
conversion
Current input
Rated input
range
±20 mA
0m A~20 mA
4 mA~20 mA
Hardware
input range
-20.2 mA~20.2 mA
-0.2 mA~20.2 mA
3.8 mA~20.2 mA
Hardware
resolution
16 bits
Input
impedance
250
Ω
Absolute
input range
±32 mA
AH04DA-5A/AH08DA-5B
The electrical specifications
Module name
AH04DA-5A
AH08DA-5B
Number of outputs
4 8
Analog-to-digital
conversion
Voltage output/Current output
Voltage output
Supply voltage
24 V DC (20.4 V DC~28.8 V DC) (-15%~+20%)
Connector type
Removable terminal block
Overall accuracy
25°C/77°F: The error is
0.5% of the input within the range
-20~60°C/-4~140°F: The error is
1% of the input within the range
Conversion time
150
μ
s/channel
There is isolation between a digital circuit and an analog circuit, but
there is no isolation between analog channels.
Isolation
Isolation between a digital circuit and a ground: 500 V DC
Isolation between an analog circuit and a ground: 500 V DC
Isolation between an analog circuit and a digital circuit: 500 V DC
Isolation between the 24 V DC and a ground: 500 V DC
3-33
Summary of Contents for AH02HC-5A
Page 1: ......
Page 13: ...AH500 Hardware Manual Step 1 Setting the PLC to RUN Step 2 Entering the on line mode 1 12...
Page 33: ...3 2 3 11 1 Profiles 3 73 3 11 2 Dimensions 3 74...
Page 181: ...Chapter 5 OOWiring 5 68 MEMO...
Page 189: ...AH500 Hardware Manual MEMO 7 4...
Page 195: ...AH500 Hardware Manual MEMO 8 6...
Page 229: ...AH500 Hardware Manual MEMO 9 34...