AH500 Hardware Manual
9.1
Troubleshooting for CPU Modules
Users can get the remedies from the tables below according to the statuses of the LED indicators
and the error codes.
9.1.1
ERROR LED Indicator’s Being ON
Error
code
Description
Remedy
16#000B
The program in the PLC is
damaged.
Download the program again.
16#000D
The CPU parameter is
damaged.
Reset the CPU parameter, and download it.
16#0010
The access to the memory in
the CPU is denied.
Download the program or parameters again. If the
problem still occurs, please contact the factory.
16#0011 The PLC ID is incorrect. (SM9)
Please check the PLC ID.
16#0012
The PLC password is
incorrect. (SM9)
Please check the PLC password.
16#0014
The procedure of restoring the
system can not be executed.
(SM9)
The contents of the system backup file are incorrect,
or the file does not exist in the path specified. If the
file exists and the procedure of restoring the system
can not be executed, please backing up the system
again. If the error still occurs, please contact the
factory. (Please refer to section 7.5 in AH500
Operation Manual, and section 18.2 in ISPSoft User
Manual for more information about the memory
card.)
16#0015
The module table is incorrect.
(SM10)
The module table stored in the CPU module is
incorrect. Compare the module table in HWCONFIG
with the actual module configuration, and download
the module table again.
16#0016
The module setting is
incorrect. (SM10)
The module setting stored in the CPU module is
incorrect. Check whether the version of the module
inserted in the slot is the same as the version of the
module in HWCONFIG. After the version of the
module is updated, users can download the module
setting again.
16#0017
The data register exceeds the
device range. (SM10)
The data register stored in the CPU module exceeds
the device range. Check whether the module
parameter in HWCONFIG is correct, and download
the module parameter again.
16#001B
Timed interrupt 0 is set
incorrectly.
Set the CPU parameter in HWCONFIG again, and
download the CPU parameter again.
16#001C
Timed interrupt 1 is set
incorrectly.
Set the CPU parameter in HWCONFIG again, and
download the CPU parameter again.
16#001D
Timed interrupt 2 is set
incorrectly.
Set the CPU parameter in HWCONFIG again, and
download the CPU parameter again.
16#001E
Timed interrupt 3 is set
incorrectly.
Set the CPU parameter in HWCONFIG again, and
download the CPU parameter again.
16#001F
The watchdog timer is set
incorrectly.
Set the CPU parameter in HWCONFIG again, and
download the CPU parameter again.
16#0020
The setting of the fixed scan
time is incorrect.
Set the CPU parameter in HWCONFIG again, and
download the CPU parameter again.
16#0021
The setting of the fixed scan
time is incorrect.
Set the CPU parameter in HWCONFIG again, and
download the CPU parameter again.
Summary of Contents for AH02HC-5A
Page 1: ......
Page 13: ...AH500 Hardware Manual Step 1 Setting the PLC to RUN Step 2 Entering the on line mode 1 12...
Page 33: ...3 2 3 11 1 Profiles 3 73 3 11 2 Dimensions 3 74...
Page 181: ...Chapter 5 OOWiring 5 68 MEMO...
Page 189: ...AH500 Hardware Manual MEMO 7 4...
Page 195: ...AH500 Hardware Manual MEMO 8 6...
Page 229: ...AH500 Hardware Manual MEMO 9 34...