Chapter 5
OOWiring
5.10.4.2
Wiring the Output Terminals
1.
The transistor output circuit
Transistor output
Load
T r i
g g
e r
c i r
c u
i t
Y0.8
LED
C0
< 0.5A
Direct-current power supply
Emergency stop
Fuse
The transistor outputs are open collectors. If Y0.8 is a pulse output, the output current passing
through the output pull-up resistor must be larger than 0.1 A to ensure that the transistor
operates normally.
Relay/Solenoid valve through which the direct current passes: A diode is connected in parallel
to absorb the surge voltage which occurs when the load is OFF.
Bulb (incandescent lamp) through which the direct current passes: A thermistor is connected in
series to absorb the surge current which occurs when the load is ON.
Y0.9 can not be connected to the power supply directly. The output wiring has to be connected
to a load.