AH500 Hardware Manual
Error
Description
Remedy
code
16#600B
UDP connection failure
(SM1091)
1. Check the actual network configuration, and
check whether the number of UDP connections
exceeds the upper limit supported by the CPU
module.
2. Retry the TCP connection later. (This error does
not cause the PLC to stop running. Users can
perform the corresponding remedy by means of
the related flag in the program.)
16#600C
The TCP socket has been
used. (SM1109)
1. Check whether the actual data access results in
the use of the same socket.
2. Change the socket number, or retry the socket
later. (This error does not cause the PLC to stop
running. Users can perform the corresponding
remedy by means of the related flag in the
program.)
16#600D
The RJ45 port is not
connected.
Check the communication cable.
16#6100
The email connection is busy.
(SM1113)
Retry the email connection later. (This error does
not cause the PLC to stop running. Users can
perform the corresponding remedy by means of
the related flag in the program.)
16#6104
The attachment in the email
does not exist. (SM1113)
Check whether the attachment exists in the
memory card.
16#6105
The attachment in the email is
oversized. (SM1113)
Check the size of the file which is specified as the
attachment. If the size is over 2 MB, the file can
not be specified as the attachment.
16#6107
There is an SMTP server
response timeout. (SM1113)
1. Check whether the status of the SMTP server is
normal.
2. Retry the sending of the email later. (This error
does not cause the PLC to stop running. Users
can perform the corresponding remedy by
means of the related flag in the program.)
16#6201
The local communication port
set in the TCP socket function
is illegal.
1. Check the program and the related special data
registers.
2. Set the Ethernet parameter for the CPU module
in HWCONFIG again.
16#6202
The remote communication
port set in the TCP socket
function is illegal.
1. Check the program and the related special data
registers.
2. Set the Ethernet parameter for the CPU module
in HWCONFIG again.
16#6203
The device from which the data
is sent in the TCP socket
function is illegal.
1. Check the program and the related special data
registers.
2. Set the Ethernet parameter for the CPU module
in HWCONFIG again.
16#6204
The transmitted data length set
in the TCP socket function is
illegal.
1. Check the program and the related special data
registers.
2. Set the Ethernet parameter for the CPU module
in HWCONFIG again.
16#6205
The data which is sent through
the TCP socket exceeds the
device range.
1. Check the program and the related special data
registers.
2. Set the Ethernet parameter for the CPU module
in HWCONFIG again.
9-12
Summary of Contents for AH02HC-5A
Page 1: ......
Page 13: ...AH500 Hardware Manual Step 1 Setting the PLC to RUN Step 2 Entering the on line mode 1 12...
Page 33: ...3 2 3 11 1 Profiles 3 73 3 11 2 Dimensions 3 74...
Page 181: ...Chapter 5 OOWiring 5 68 MEMO...
Page 189: ...AH500 Hardware Manual MEMO 7 4...
Page 195: ...AH500 Hardware Manual MEMO 8 6...
Page 229: ...AH500 Hardware Manual MEMO 9 34...