16#630A
The module ID or the setting
of the module is different from
the setting in the Ether Link.
1. Check the setting of the parameter in
HWCONFIG.
2. Check the setting of the Ether Link in
NWCONFIG.
16#630B
The setting of the netmask
address for the CPU or the
module is different from the
setting in the Ether Link.
1. Check the setting of the parameter in
HWCONFIG.
2. Check the setting of the Ether Link in
NWCONFIG.
16#6602
The node number exceeds
the limit. (SM1598)
Check the network configuration in NWCONFIG,
and download it again.
16#6603
The device is undefined.
(SM1599)
Check the network configuration in NWCONFIG,
and download it again.
16#8230
The CPU parameter
downloaded is incorrect.
The IP address is illegal.
1. Check the Ethernet parameter in the CPU
module in HWCONFIG.
2. Check whether the version of HWCONFIG used
now is compatible with the version of the CPU.
16#8231
The CPU parameter
downloaded is incorrect.
The netmask address is
illegal.
1. Check the Ethernet parameter in the CPU
module in HWCONFIG.
2. Check whether the version of HWCONFIG used
now is compatible with the version of the CPU.
16#8232
The CPU parameter
downloaded is incorrect.
The gateway address is
illegal.
1. Check the Ethernet parameter in the CPU
module in HWCONFIG.
2. Check whether the version of HWCONFIG used
now is compatible with the version of the CPU.
16#8233
The CPU parameter
downloaded is incorrect.
The IP address filter is set
incorrectly.
1. Check the Ethernet parameter in the CPU
module in HWCONFIG.
2. Check whether the version of HWCONFIG used
now is compatible with the version of the CPU.
16#8235
The CPU parameter
downloaded is incorrect.
The static ARP table is set
incorrectly.
1. Check the Ethernet parameter in the CPU
module in HWCONFIG.
2. Check whether the version of HWCONFIG used
now is compatible with the version of the CPU.
16#8237
The CPU parameter
downloaded is incorrect.
The network number is illegal.
1. Check the network configuration in NWCONFIG.
2. Check whether the version of HWCONFIG used
now is compatible with the version of the CPU.
16#8238
The CPU parameter
downloaded is incorrect.
The node number is illegal.
1. Check the network configuration in NWCONFIG.
2. Check whether the version of HWCONFIG used
now is compatible with the version of the CPU.
16#8239
The CPU parameter
downloaded is incorrect.
The email is set incorrectly.
1. Check the Ethernet parameter in the CPU
module in HWCONFIG.
2. Check whether the version of HWCONFIG used
now is compatible with the version of the CPU.
16#823A
The CPU parameter
downloaded is incorrect.
The trigger in the email is set
incorrectly.
1. Check the Ethernet parameter in the CPU
module in HWCONFIG.
2. Check whether the version of HWCONFIG used
now is compatible with the version of the CPU.
16#823B
The CPU parameter
downloaded is incorrect.
The TCP socket is set
incorrectly.
1. Check the Ethernet parameter in the CPU
module in HWCONFIG.
2. Check whether the version of HWCONFIG used
now is compatible with the version of the CPU.
9-9
Summary of Contents for AH02HC-5A
Page 1: ......
Page 13: ...AH500 Hardware Manual Step 1 Setting the PLC to RUN Step 2 Entering the on line mode 1 12...
Page 33: ...3 2 3 11 1 Profiles 3 73 3 11 2 Dimensions 3 74...
Page 181: ...Chapter 5 OOWiring 5 68 MEMO...
Page 189: ...AH500 Hardware Manual MEMO 7 4...
Page 195: ...AH500 Hardware Manual MEMO 8 6...
Page 229: ...AH500 Hardware Manual MEMO 9 34...