4. Setting up the device
12
Display overflow,
dI.OUE:
With this function the display overflow (
_ _ _ _ _
) can be defined on a definite value.
Device undercut,
dI.Und:
With this function the device undercut (
_ _ _ _ _
) can be defined on a definite value.
Exception is input type
4-20 mA
, it already shows undercut at a signal <1 mA, so a
sensor failure is marked.
Analog values for setpoints,
InP.01 … InP.30:
The setpoints are allways set according to the selected input signal. The desired
analog values can be freely parameterised in ascending order.
Back to menu group level,
rEt:
With
[P]
the selection is confirmed and the device changes into menu group
level
„–INP-“
.
Display values for setpoints,
dIS.01 … dIS.30:
Under this parameter setpoints are defined according to their value. At the sensor
calibration, like at Endwert/Offset, one is asked at the end if a calibration shall be
activated.
Number of additional setpoints,
SPCt:
30 additional setpoints can be defined to the initial- and final value, so linear sensor
values are not linearised. Only activated setpoint parameters are displayed.
Parameterisation level
Menu level