4. Setting up the device
26
Switching-off delay,
toF-1:
For limit value 1 one can preset a delayed switching-off of 0-100 seconds.
Switching-on delay,
ton-1:
For limit value 1 one can preset a delayed switching-on of 0-100 seconds.
Function for threshold value undercut /exceedance,
Fu-1:
A limit value undercut is selected with
Louu
(for LOW = lower limit value), a limit value
exceedance with
High
(for HIGH = higher limit value). If e.g. limit value 1 is on a
threshold level of 100 and allocated with function
High
, an alarm is activated by
reaching of the threshold level. If the threshold value was allocated to
Low,
an alarm
will be activated by undercutting the threshold value, as long as the hysteresis is zero.
Hysteresis for Threshold values,
HY-1:
The delayed reaction of the alarm is the difference to the threshold value, which is
defined by the hysteresis.
Threshold values / Limit values,
LI-1:
The limit value defines the threshold, that activates/deactivates an alarm.
Back to menu group level,
rEt
:
With
[P]
the selection is confirmed and the device changes into menu group
level
„– Al1 –“
.
Parameterisation level
Menu level
The same applies for
–Al2–
to
–Al8–
.