Decentral Solutions
Programming, FCD
300
■
Technical functions
NOTE
Parameters 615-617
Fault log
cannot be read
out via the integral control unit.
615 Fault log: Error code
(F.LOG: ERROR COD)
Value:
[Index 1 - 10] Error code: 0 - 99
Function:
In this parameter it is possible to see the reason
for a trip (cut-out of the variable frequency drive)
occurring. 10 [1-10] log values are defined.
The lowest log number [1] contains the latest/most
recently saved data value. The highest log number [10]
contains the oldest data value saved. If a trip occurs,
it is possible to see the cause, time and a possible
value of the output current or output voltage.
Description of choice:
Given as a fault code, in which the number refers to a
table. See the table in
Warnings/alarm messages
.
616 Fault log: Time
(F.LOG: TIME)
Value:
[Index 1 - 10] Hours: 0 - 130,000.0
Function:
In this parameter it is possible to see the total number
of operating hours in connection with the last 10 trips.
10 [1-10] log values are denoted. The lowest
log number [1] contains the latest/most recently
saved data value, and the highest log number
[10] contains the oldest data value.
Description of choice:
Read out as one value.
617 Fault log: Value
(F.LOG: VALUE)
Value:
[Index 1 - 10] Value: 0 - 9999
Function:
In this parameter it is possible to see at which value a
trip occurred. The unit of the value depends on which
alarm is active in parameter 615
Fault log: Fault code
.
Description of choice:
Read out as one value.
618 Reset of kWh counter
(RESET KWH COUNT)
Value:
✭
No reset (DO NOT RESET)
[0]
Reset (RESET COUNTER)
[1]
Function:
Resetting parameter 602
kWh counter
to zero.
Description of choice:
If
Reset
[1]is selected and you press the [OK]
key, the variable frequency drive
’
s kWh counter
is reset to zero. This parameter cannot be
selected via serial communication.
NOTE
When the [OK] key is activated, the
counter is reset to zero.
619 RESET RUNNING HOURS COUNTER
(RESET RUN. HOUR)
Value:
✭
No reset (DO NOT RESET)
[0]
Reset (RESET COUNTER)
[1]
Function:
Resetting of parameter 601
Hours run
to zero.
Description of choice:
If
Reset
[1] is selected and you press the [OK] key,
the variable frequency drive
’
s parameter 601 is
reset to zero
Hours run
. This parameter cannot
be selected via serial communication.
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.90.F2.22 - VLT is a registered Danfoss trademark
169