Decentral Solutions
Use of the relay for 230 V AC brake
Par. 302
Digital input
=
Start
[7]
Par. 304
Digital input
=
Coasting stop inverted
[2]
Par. 323
Relay output
=
Mechanical
brake control
[25]
See also par. 138, 139, 140
Mechanical brake control
[25] =
’
0
’
=> Brake is closed.
Mechanical brake control
[25] =
’
1
’
=> The brake is open.
See more detailed parameter settings under
Control of mechanical brake
.
NOTE
Do not use the internal relay for DC brakes
or brake voltages > 250 V.
■
Counter stop via terminal 33
The start signal (terminal 18) must be active, i.e. logical
’
1
’
, until the output frequency is equal to the reference.
The start signal (terminal 18 = logical
’
0
’
) must then be
removed before the counter value in parameter 344
has managed to stop the VLT frequency converter.
Par. 307
Digital input
=
Pulse input
[30]
Par. 343
Precise stop function
=
Counter
stop with reset
[1]
Par. 344
Counter value
= 100000