Decentral Solutions
505 Start
(START SELECT)
Value:
Digital input (DIGITAL INPUT)
[0]
Serial port (SERIAL PORT)
[1]
Logic and (LOGIC AND)
[2]
✭
Logic or (LOGIC OR)
[3]
Function:
See function description for parameter 502
Coasting stop.
Description of choice:
The table below shows when the motor has stopped
and when the variable frequency drive has a start
command when each of the following is selected:
Digital
input
[0],
Serial port
[1],
Logic and
[2] or
Logic or
[3].
Digital input
[0]
Dig. input
Ser. port
Function
0
0
Stop
0
1
Stop
1
0
Start
1
1
Start
Serial port
[1]
Dig. input
Ser. port
Function
0
0
Stop
0
1
Start
1
0
Stop
1
1
Start
Logic and
[2]
Dig. input
Ser. port
Function
0
0
Stop
0
1
Stop
1
0
Stop
1
1
Start
Logic or
[3]
Dig. input
Ser. port
Function
0
0
Stop
0
1
Start
1
0
Start
1
1
Start
506 Reverse
(REVERSE SELECT)
Value:
Digital input (DIGITAL INPUT)
[0]
Serial port (SERIAL PORT)
[1]
Logic and (LOGIC AND)
[2]
✭
Logic or (LOGIC OR)
[3]
Function:
See function description for parameter 502
Coasting stop.
Description of choice:
The table below shows when the motor is running
clockwise and counter-clockwise when each of
the following is selected:
Digital input
[0],
Serial
port
[1],
Logic and
[2] or
Logic or
[3].
Digital input
[0]
Dig. input
Ser. port
Function
0
0
Clockwise
0
1
Clockwise
1
0
Counter-clockwise
1
1
Counter-clockwise
Serial port
[1]
Dig. input
Ser. port
Function
0
0
Clockwise
0
1
Counter-clockwise
1
0
Clockwise
1
1
Counter-clockwise
Logic and
[2]
Dig. input
Ser. port
Function
0
0
Clockwise
0
1
Clockwise
1
0
Clockwise
1
1
Counter-clockwise
Logic or
[3]
Dig. input
Ser. port
Function
0
0
Clockwise
0
1
Counter-clockwise
1
0
Counter-clockwise
1
1
Counter-clockwise
✭
= factory setting. () = display text [] = value for use in communication via serial communication port