Decentral Solutions
IEC/EN 61000-4-5:
Surge immunity test.
Simulation of Surge Voltages disturbances caused
by switching and lightning phenomena on power
and interconnection lines.
IEC/EN 61000-4-6:
Immunity to conducted
disturbances, induced by radio-frequency fields.
IEC/EN 61000-4-11:
Voltage dips, short interruptions
and voltage variations immunity tests.
VDE 0160 (1990):
Test with high-energy
class W2 test pulse.
Simulation of high-energy voltage disturbances caused
by break in master fuses in power line installations.
Basic standard
Burst
61000-4-4
Surge
61000-4-5
ESD
61000-4-2
Radiated
61000-4-3
AC lines
distortion
VDE 0160
RF in
voltage
2
61000-4-6
Acceptance
criterion
B
B
B
A
A
Port connection
CM
DM / CM
Field
DM
CM
Line
OK/OK
OK
Motor
OK
Control lines
OK
- / OK
1
OK
Relay
OK
- / OK
OK
Profibus
OK
- / OK
1
OK
Signal interface
<10 ft (3 m)
OK
Enclosure
OK
OK
Standard bus
OK
- / OK
1
OK
Basic speci-
fications
Line
2 kV / DCN
1 kV / 2 kV
10 Vrms
Motor
10 Vrms
Control lines
2 kV / CCC
- / 4 kV, 2
1
10 Vrms
Relay
2 kV / CCC
- / 1kV, 2
10 Vrms
Profibus
2 kV / CCC
- / 4 kV, 2
1
10 Vrms
Signal interface
<10 ft (3 m)
2 kV / CCC
Enclosure
8 kV AD
6 kV DC
3 V/ft (10
V/m)
Standard bus
2 kV / CCC
- / 4 kV, 2
1
10 Vrms
DM: Differential mode
CM: Common mode
CCC: Capacitive clamp coupling (5 kHz)
DCN: Direct coupling network (5 kHz)
1. Injection on cable shield.
2. Electromagnetic clamp.
MG.90.F2.22 - VLT is a registered Danfoss trademark
186