Decentral Solutions
Specification and
order codes, DMS 300
■
Ordering type code
The DMS is available in the following variants:
-
Standard
-
Standard with Brake
-
Extended
-
Extended with Brake
-
Extended with Brake & Reverse
The Extended varaints are available with integrated
Fieldbus AS-i interface. The extended versions can be
delivered with Profibus interface including 4 additional
M12 plugs for connection of external sensors.
Refer to the table for the Part numbers
corresponding to the variants.
For example, the part number for a Motor Mount
DMS unit, with Reverse function, and without
Fieldbus connection would be:
DMS330PT4P66ERD0F00T12C0
■
Certifications
The DMS 300 has CE, UL, cUL and C-tick
certifications. The details are as under:
CE
Rated insulation voltage ............................................................................................................................ 500 VAC
Rated impulse withstand ........................................................................................... 2.0 kV (1.2/ 50 micro second)
Conducted and radiated frequency emissions ................................................................ Class B as per EN 55011
Electrostatic discharge, 4 kV contact and 8 kV air discharge ................................................ no effect on operation
Radio frequency electromagnetic field, 0.15 MHz to 1.0 GHz ................................................ no effect on operation
Fast transients, 2.0 kV/ 5.0 kHz ............................................................................................ no effect on operation
Surges, 2.0 kV line to earth, 1.0 kV line to line ...................................................................... no effect on operation
Voltage dips and short interruptions ...................................................................................... no effect on operation
Short circuit tested on 5 kA supply, when protected by semiconductor fuses (Type 2 co-ordination) ................... no
damage to DMS 300, no danger to persons or installation
Short circuit tested on 5 kA supply, when protected by HRC fuses (Type 1 co-ordination) ................................... no
danger to persons or installation, DMS unit may be unsuitable for future use
UL
C-tick
IP66
To maintain certifications, the product shall not be
modified an any way, shall be used only for the specified
purpose, and must be installed according to this manual
and/or any other authorized Danfoss instruction.
■
Fuses
The DMS 300 should be used with suitable fusing as
per the co-ordination requirements of the circuit..
Max pre-fuses: DMS 300 meets Type 1 co-ordination
with properly rated HRC fuses.
Use type gG 25A, 415 VAC or equivalent HRC fuses.
Semiconductor fuses are required to meet
UL, C-UL Certification.
Semiconductor fuses listed below are manufactured
by Bussmann and should be ordered directly from
Bussmann or their local supplier.
Bussmann, High Speed fuse, Square body, Size 000,
660 V, 20 Amps rated - Part no: 170 M 1310
or
Bussmann, British style, BS88, Type CT, 690 V,
20 Amps rated - Part no: 20CT
MG.90.F2.22 - VLT is a registered Danfoss trademark
57