Decentral Solutions
Selection of Setup, lsb
and
Selection of Setup,
msb
gives the possibility to select one of the
four setups. It is, however, a condition that
parameter 004 is set to
Multisetup
.
Reset and start
can be used as a start function. If 24
V are connected to the digital input, this will cause
the variable frequency drive to reset and the motor
will ramp up to the preset reference.
Encoder reference
is selected if the reference
signal applied is a pulse train (frequency). 0 Hz
corresponds to parameter 204
Minimum reference,
Ref
MIN
. The frequency set in parameter 327/328
Pulse Max 33/29
corresponds to parameter 205
Maximum reference Ref
MAX
.
Encoder feedback
is selected if the feedback signal
used is a pulse train (frequency). In parameter
327/328
Pulse Max 33/29
the maximum pulse
feedback frequency is set.
Encoder input
is selected if a specific number of pulses
must lead to a
Precise stop
, see parameter 343
Precise stop
and parameter 344
Counter value
.
All encoder settings are used in connection with dual
track encoders with direction recognition.
A track connected to terminal 29.
B track connected to terminal 33.
308 Terminal 53, analog input voltage
(AI [V]53FUNCT.)
Value:
No function (NO OPERATION)
[0]
✭
REFERENCE % (REFERENCE %)
[1]
Feedback (FEEDBACK)
[2]
Function:
In this parameter it is possible to select the function
required to be connected to terminal 53. Scaling of the
input signal is made in parameter 309
Terminal 53, min.
scaling
and parameter 310
Terminal 53, max. scaling
.
Description of choice:
No function
[0]. Is selected if the variable frequency
drive is not to react to signals connected to the terminal.
Reference
[1]. If this function is selected, the reference
can be changed by means of an analog reference
signal. If reference signals are connected to more than
one input, these reference signals must be added up.
If a voltage feedback signal is connected, select
Feedback
[2] on terminal 53.
309
Terminal 53 Min. scaling
(AI 53 SCALE LOW)
Value:
0.0 - 10.0 Volt
✭
0.0 Volt
Function:
This parameter is used for setting the signal value
that is to correspond to the minimum reference or
the minimum feedback, parameter 204
Minimum
reference, Ref
MIN
/ 414
Minimum feedback, FB
MIN
.
Description of choice:
Set the required voltage value. For reasons of accuracy,
compensation should be made for voltage loss in long
signal cables. If the Time out function is to be used
(parameter 317
Time out
and 318
Function after time
out
), the value set must be higher than 1 Volt.
310
Terminal 53 Max. scaling
(AI 53 SCALE HIGH)
Value:
0 - 10.0 Volt
✭
10.0 Volt
Function:
This parameter is used for setting the signal value
that is to correspond to the maximum reference value
or maximum feedback, parameter 205
Maximum
reference, Ref
MAX
/ 414
Maximum feedback, FB
MAX
.
Description of choice:
Set the required voltage value. For reasons of
accuracy, compensation should be made for
voltage losses in long signal cables.
314 Terminal 60, analog input current
(AI [MA] 60 FUNCT)
Value:
✭
No function (NO OPERATION)
[0]
REFERENCE % (REFERENCE %)
[1]
Feedback (FEEDBACK)
[2]
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.90.F2.22 - VLT is a registered Danfoss trademark